Filling; Air Pressure Differential - A.O. Smith Innovo 12-160 Installation, Service & Maintenance Manual

Condensing high-efficiency water heater
Table of Contents

Advertisement

8.9.1
8.9.2
n
n
52

Filling

Refer to the installation diagram (see section 8.3) when you fill the water heater:
1.
Open the stop valve (11) in the hot water supply pipe.
2.
If applicable, open the stop valves (4) of the circulation pipe (C).
3.
Make sure that the drain valve (9) is closed.
4.
Open the nearest hot water draw-off point (14).
5.
Open the stop valve (4) of the cold water supply pipe (A). Cold water flows into the
water heater.
6.
Fill the water heater until a full water jet flows from the nearest draw-off point. The
water heater is completely full.
7.
Open all draw-off points to bleed the entire installation of air.
The water heater is now under water supply pressure.
8.
Make sure that no water comes out of the expansion valve (15) or the T&P valve (3).
If water comes out:
-
Examine if the water supply pressure is greater than the specified value in the
Technical details (see section 13.1). If necessary, install a pressure reducing
valve (1).
-
Examine if the expansion valve in the protected cold supply set-up is installed
correctly and is not defect. If necessary, replace the expansion valve.

Air pressure differential

Check the air pressure differential across the air pressure switch:
1.
Disconnect hose H of the air proving switch and connect this side of the hose to the
+ of the pressure gauge.
2.
Disconnect hose L of the air pressure switch and connect this side of the hose to the
- of the pressure gauge.
3.
Turn the water heater on and set the water heater in OFF mode, refer to Turn on
the water heater (see section 4.2).
Note
Make sure that the water heater is not in ON mode or in External ON mode.
4.
Set parameter 201 to FAn, refer to Settings (see section 10).
5.
Read the pressure value from the meter.
6.
Compare the measured value to the value from the table (see section 13.1).
Note
When the air pressure differential is not correct, refer to Displayed errors (see section
12.1.2), error F03.
7.
Set parameter 201 to dIS, refer to Settings (see section 10).
8.
Press [RESET].
The water heater goes into OFF mode.
9.
Set the control switch on the side of the water heater to 0 to turn off the water
heater.
10.
Disconnect the pressure gauge.
11.
Reconnect the hoses of the air proving switch and the gas valve.
Installation, Maintenance and Service part

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents