5
WIRING DIAGRAM
PCA-A24KA7
PCA-A30KA7
SYMBOL
NAME
I.B
INDOOR CONTROLLER BOARD
CN2L
CONNECTOR (LOSSNAY)
CN24
CONNECTOR (BACK-UP HEATING)
CN32
CONNECTOR (REMOTE SWITCH)
CN41
CONNECTOR (HA TERMINAL-A)
CN51
CONNECTOR (CENTRALLY CONTROL)
CN105
CONNECTOR
FUSE
FUSE (T6.3AL250V)
LED1
POWER SUPPLY (I.B)
LED2
POWER SUPPLY (R.B)
LED3
TRANSMISSION (INDOOR-OUTDOOR)
SW1
SWITCH (MODEL SELECTION) Refer to <Table 1>.
SW2
SWITCH (CAPACITY CODE) Refer to <Table 2>.
SWE
CONNECTOR (EMERGENCY OPERATION)
X1
RELAY (DRAIN PUMP)
MF
FAN MOTOR
MV
VANE MOTOR
The black square(■)indicates a switch position.
<Table 1>
<Table 2>
SW1(MODEL SELECTION)
SW2(CAPACITY CODE)
SW1
Manufacture/Service
PCA-A24KA
1 2 3 4 5
ON
OFF
PCA-A30KA
I.B
20
18
16
14
12
10
8
6
19
17
15
13
11
9
7
5
CNV
(WH)
CN90
CN4Y
(WH)
(WH)
1
4
1
9
4
9
5
CNB
BZ
I-SEE
SENSOR
M
I-SEE SENSOR
SW1
LED2
(OPTION PART)
MV
SW2
LED1
RU
W.B
(OPTION PART)
Notes:
1.SymboIs used in wiring diagram above are,
2.Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3).
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 208V/230V), adopting superimposed
system of power and signal.
● For power supply system of this unit, refer to the caution label located near this diagram.
1:Use copper supply wire.
Utilisez des fils d'alimentation en cuivre.
Due to continuing improvement, above specification may be subject to change without notice.
© 2017 Mitsubishi Electric US, Inc.
PCA-A36KA7
SYMBOL
TB4
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TB5
TRANSMISSION LINE)
TH1
ROOM TEMP. THERMISTOR
(32ºF / 15kΩ, 77ºF / 5.4kΩ DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(32ºF / 15kΩ, 77ºF / 5.4kΩ DETECT)
TH5
COND. / EVA. TEMP. THERMISTOR
(32ºF / 15kΩ, 77ºF / 5.4kΩ DETECT)
OPTION PARTS
W.B
PCB FOR IR WIRELESS REMOTE CONTROLLER
BZ
BUZZER
LED1
LED (OPERATION INDICATION : GREEN)
LED2
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
RU
SW1
EMERGENCY OPERATION (HEAT)
SW2
EMERGENCY OPERATION (COOL)
DP
DRAIN PUMP
FS
DRAIN FLOAT SWITCH
R.B
WIRED REMOTE CONTROLLER BOARD
TB6
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
MT
I-SEE SENSOR MOTOR
SW2
MODELS
Manufacture/Service
MODELS
Manufacture/Service
1 2 3 4 5
PCA-A36KA
ON
OFF
1 2 3 4 5
PCA-A42KA
ON
OFF
Refer to tables 1 and 2
J41
J42
4
2
SW1
SW2
3
1
Pair No.
CN2L
(RD)
2 1
LED3
LED2
LED1
CN6Y
CN105
CN4F
(RD)
(RD)
(WH)
1
6
1
5
1
5
When attaching
M
drain pump
(Option part),
MT
remove the
jumper
connector
CN4F and fit
the drain float
switch (FS).
:Connector,
PCA-A42KA7
NAME
TB5
1 2 3 4 5
1
ON
2
OFF
TRANSMISSION
WIRES
1 2 3 4 5
ON
DC12V
OFF
2
CN32
(WH)
1
3
1 3
CN24
CN3C
CN51(WH)
(YE)
(BU)
5
1
2
1
CN41(WH)
1
2
CN22
4
1
(BU)
SWE
ON OFF
CN44
CN20
(WH)
(RD)
4
1
4
1
2
When attaching
TH2 TH5
TH1
drain pump
Be sure to turn off the source power
(Option part)
1
4
and then disconnect fan motor connector CNMF.
CN4F
(WH)
(Failure to do so will cause trouble in fan motor)
FS
:Terminal block.
P-Series (March 2017)
(OPTION PART)
R.B
TB4
TB6
YE
YE
1
OG
OG
2
OG
BN
1 3 5
CN01
(BK)
FUSE
X1
CNMF
(WH)
3
1
7
4
1
CNP
(BU)
M
MS
3~
1~
DP (OPTION PART)
MF
1
S1
TO OUTDOOR
S2
UNIT
S3
41

Hide quick links: