4.2
Level 2
Main Control
Proportional Band
SET
Main Control
Integral Time
SET
Main Control
Derivative Time
SET
Main Control
Dead-band Time
SET
Main Control
Auto Tuning off-set
SET
Main Control
Proportional Cycle
SET
Main Control
Hysterisis
SET
Sub Control
Proportional band
SET
Sub Control
Integral Time
SET
Sub Control
Derivative Time
SET
Sub Control
Proportional Cycle
SET
Sub Control
Hysterisis
SET
Main Control
Gap (Output 1)
SET
Sub Control
Gap (Output 2)
SET
Function Lock
LCK=0000, To enter any Level(except SET Level) and to change their parameters
SET
LCK=0100, To enter Level 1 & 2 and to change their parameters
Return to
LCK=0110, To enter Level 1 & 2 and to change the parameters on Level 1 allowed.
LCK=0001, To enter Level 1 only and to change SP allowed.
'P1'
LCK=0101, Nothing allowed except to change LCK.
DC1010/1020/1030/1040 PRODUCT MANUAL
Range: 0.0~200.0%
ON/OFF at P1=0
Range: 0~3600 sec
Integral off at I=0
Range: 0~900 sec
Derivative off at D=0
Don't care.
Range: 0~USPL
Output (SSR
1, 4~20mA 0, relay over 10)
Range: 0~150 sec * Refer to 8.10 Cycle Time
For ON/OFF control(P1=0) only(Range: 0~1000)
OFF : PV>(SP+HYS1)
ON : PV<=(SP-HYS1)
Same as P1
ON/OFF at P2=0
Same as I1
Same as D1
Same as CYT1
Same as HYS1
For dual output use only, set the value turning
Turning Point = SP-GAP1 ; OFF
For dual output use only, set the value turning
Turning Point = SP+GAP2 ; ON
* Refer to 4.4.1(P.7)
4
allowed.