Recooling Unit" Screen; Power Cells" Screen - Siemens SIMATIC HMI TP900 Operator's Manual

Hide thumbs Also See for SIMATIC HMI TP900:
Table of Contents

Advertisement

4.2.2

"Recooling Unit" screen

The "Recooling Unit" screen displays the following information:
● The current values of the cooling system
● The current status of the pumps
● The current status of the deionizer
● The current status of the expansion tank
Calling the screen
Press the "Status" button in the navigation bar. Select the "Recooling Unit" screen.
Figure 4-3
The following standard limit values are shown in red. They are fixed values on the screen, not
parameters.
● Water temperature: < 10° C, > 46° C. The value can be adapted to the specific project.
● Differential pressure: < 3 bar, > 4 bar
● Conductivity: < -1 μS/cm, > 1.2 μS/cm
4.2.3

"Power Cells" screen

The "Power Cells" screen displays the following information:
● The cell status
● The cell ID
The cell ID is required for resetting and repairing the cell bypass.
TP900 Function Manual
Function Manual, 10/2016, A5E39487277A
Example: "Recooling Unit" screen, double-circuit