Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 85

Digital boiler control unit
Table of Contents

Advertisement

Vitotronic 200, HO1B and 300-K, MW2C Installation/Service
"General" Group
Coding in the factory set condition
"Wintertime starts: Day of the selected month"
87:7
Wintertime starts:
Last Sunday of the selected month
"Temperature displayed"
88:0
Temperature unit °C (Celsius)
"Boiler connection"
89:0
Boiler communication KMK
"Test display conditions"
8a:175
Do not adjust!
"Operation enabled/blocked"
8f:0
Cannot be adjusted
"Time constant for calculating adjusted outdoor temperature"
90:36
Time constant for calculating the adjusted
outdoor temperature 6 h
"Connection at terminals 1 and 2 in plug avD"
91:0
Connection at terminals 1 and 2 in plug
avD disabled (external heating program
changeover) (see page 24)
"Communication interface"
95:0
Without Vitocom 100, type GSM2
communication interface
"Extension for heating circuits 2 and 3 with mixing valve"
96:1
With extension PCB for heating circuits 2
and 3; automatic recognition.
"With LON communication module: Outdoor temp"
97:0
The outdoor temperature of the sensor
connected to the control unit is only
utilized internally.
"Viessmann system number"
98:1
Viessmann system number (in conjunction
with monitoring several systems within
one LON system with Vitocom 300)
(continued)
Possible change
87:1
Monday to Sunday
to
87:7
88:1
Temperature unit °F (Fahrenheit)
89:1
Boiler communication LON
--
--
8f:1
Cannot be adjusted
8f:2
Cannot be adjusted
90:1
Fast (low values) or slow (high values) matching
to
of the supply temperature, subject to the set value
90:199
when the outdoor temperature changes;
1 step
10 min
91:1
Contact affects the following heating circuits:
Heating circuit without mixing valve A1 (heating
circuit 1).
91:2
Heating circuit with mixing valve M2 (heating circuit 2).
91:3
Heating circuit without mixing valve A1 (heating
circuit 1) and heating circuit with mixing valve M2
(heating circuit 2).
91:4
Heating circuit with mixing valve M3 (heating circuit 3).
91:5
Heating circuit without mixing valve A1 (heating
circuit 1) and heating circuit with mixing valve M3
(heating circuit 3).
91:6
Heating circuits with mixing valve M2 (heating circuit
2) and M3 (heating circuit 3).
91:7
Heating circuit without mixing valve A1 (heating
circuit 1) and heating circuits with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3).
95:1
With Vitocom 100, type GSM2 communication
interface; automatic recognition.
96:0
Without extension PCB for heating circuits 2 and 3.
97:1
The control unit receives the outdoor temperature
from the Vitotronic 200-H.
97:2
With LON communication module:
The control unit sends the outdoor temperature to
the Vitotronic 200-H.
98:1
System number adjustable from 1 to 5
to
98:5
Coding 2 Vitotronic 300-K
85