Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 82

Digital boiler control unit
Table of Contents

Advertisement

Coding 2 Vitotronic 300-K
"General" Group
Coding in the factory set condition
"Connection at plug sÖA1"
4c:0
Connection at plug sÖA1:
heating circuit pump.
"Delay off time, shunt or distribution pump"
4f:5
Distribution pump delay off time 5 min.
"ON integral threshold value of external heat"
50:10
On integral threshold value of external
heat set to 10 K x min.
"OFF integral threshold value of external heat"
51:255
OFF integral threshold value of external
heat set to 255 K x min.
"Solar thermal system"
54:0
Without solar thermal system
"EA1 extension"
5b:0
Without extension EA1.
"Function output aBJ at EA1 extension"
5c:0
Function output aBJ at extension EA1:
central fault message.
"Function input DE1 at EA1 extension"
5d:0
Function input DE1 at extension EA1:
No function.
82
(continued)
Vitotronic 200, HO1B and 300-K, MW2C Installation/Service
Possible change
4c:1
Primary pump, primary store system.
4f:0
No pump delay off.
4f:1
Delay off time adjustable from 1 to 60 min.
to
4f:60
50:1
On integral threshold value of external heat adjustable
to
from 1 to 255 K x min.
50:255
51:1
OFF integral threshold value of external heat adjustable
to
from 1 to 255 K x min.
51:255
54:1
With Vitosolic 100 (automatic recognition)
54:2
With Vitosolic 200 (automatic recognition)
54:3
With solar control module SM1 without auxiliary
function (automatic recognition)
54:4
With solar control module SM1 with auxiliary function,
e.g. central heating backup (automatic recognition)
5b:1
With extension EA1; automatic recognition.
5c:1
Accessories pump.
5c:2
No function.
5c:3
Heating circuit pump A1 is switched to low speed
(reduced mode).
5c:4
Heating circuit pump M2 is switched to low speed
(reduced mode).
5c:5
Heating circuit pump M3 is switched to low speed
(reduced mode).
5d:1
Operating program changeover.
5d:2
External demand with minimum set supply temperature.
Setting of the set value in coding address "9b"in the
"General" group.
5d:3
External blocking.
5d:4
External blocking with fault message.
5d:5
Fault message input.
5d:6
Brief operation, DHW recirculation pump (pushbutton
function). Setting of runtime for DHW recirculation
pump in coding address "12" in the "General" group.