Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 83

Digital boiler control unit
Table of Contents

Advertisement

Vitotronic 200, HO1B and 300-K, MW2C Installation/Service
"General" Group
Coding in the factory set condition
"Function input DE2 at EA1 extension"
5e:0
Function input DE2 at extension EA1:
No function.
"Function input DE3 at EA1 extension"
5f:0
Function input DE3 at extension EA1:
No function.
"Display correction for outdoor temperature"
6e:50
No display correction for outdoor
temperature.
"LON communication module"
76:0
Without communication module
"LON participant number"
77:9
LON participant number
"LON communication"
78:1
LON communication enabled.
"With LON communication module"
79:1
With LON communication module:
Control unit is fault manager.
(continued)
Possible change
5e:1
Operating program changeover.
5e:2
External demand with minimum set supply temperature.
Setting of the set value in coding address "9b".
5e:3
External blocking.
5e:4
External blocking with fault message.
5e:5
Fault message input.
5e:6
Brief operation, DHW recirculation pump (pushbutton
function). Setting of runtime for DHW recirculation
pump in coding address "12" in the "General" group.
5f:1
Operating program changeover.
5f:2
External demand with minimum set supply temperature.
Setting of the set value in coding address "9b".
5f:3
External blocking.
5f:4
External blocking with fault message.
5f:5
Fault message input.
5f:6
Brief operation, DHW recirculation pump (pushbutton
function). Setting of runtime for DHW recirculation
pump in coding address "12" in the "General" group.
6e:0
Display correction –5 K
to
to
6e:49
Display correction –0.1 K
6e:51
Display correction +0.1 K
to
to
6e:99
Display correction +4.9 K
76:1
With LON communication module
(automatic recognition) If no LON communication
module is installed, set coding "76:0" in the "General"
group.
77:1
LON participant number, adjustable from 1 to 99:
to
1 - 8 = Boiler
77:99
9 = Cascade
10 - 96 = Vitotronic 200-H
97 = Vitogate 300
98 = Vitogate
99 = Vitocom
78:0
LON communication disabled.
79:0
Control unit is not fault manager
Coding 2 Vitotronic 300-K
83