Operating Hour Counter; Resetting The Time Switch; Technical Data - Theben SELEKTA 170 top2 User Manual

Astro time switch
Hide thumbs Also See for SELEKTA 170 top2:

Advertisement

Activate manual switching
Briefly press both keys simultaneously
¾
Activate permanent switching
Simultaneously press both keys for 2 seconds
¾
Cancelling manual/permanent switching
Press both keys simultaneously
¾

Operating hour counter

The operating hours of the channel (relay) are displayed and
deleted in the OPTIONS menu. If the number of operating
hours exceeds the value set in the Service menu, SERVICE will
appear in the display.
Example: Replace a lamp after 5,000 h.
Delete operating hours or set a higher value in Service (e.g.
¾
to 10,000 h)
Using the OBELISK top2 memory card
L The OBELISK top2 memory card is not included in the
scope of supply of the device, but can be ordered as an
accessory (no. 9070404).
All functions can also be set on the PC using the OBELISK
software and transferred to the device via the memory card.
Insert memory card in the time switch
¾
Read in/out saved switching times and device setups in
¾
the time switch or start Obelisk program
Remove OBELISK top2 memory card after copying etc.
¾
!
Avoid mechanical overload and contamination during
storage/transport
Copy OBELISK → Time switch
Copies all switching programs and settings from the time
switch to the memory card. Starting OBELISK program
Copy Time switch → OBELISK
Copies all switching programs and settings from the time
switch to the memory card.
Start OBELISK program
ok
Takes on the switching times that are programmed on the
memory card.
As soon as the memory card is removed, the switching times
of the time switch are re-activated.
OBELISK
OBELISK -> TIME
TRANSCRIBE OK

Resetting the time switch

Press the 4 buttons simultaneously.
¾
▻ You can choose between RETAIN PROGRAM and DELETE

6. Technical Data

Operating voltage:
Frequency
Power consumption: max
Standby min
Max switching capacity.
Switching capacity
Min. switching capacity
Protection rating
Protection class
Operating temperature
Power reserve
Time accuracy
Rated impulse voltage
Pollution degree
Contact
Max. switching cycles with 16 A resistive
load
Incandescent lamp load
Halogen lamp load
Fluorescent lamps (LLB low-loss bal-
lasts):
uncorrected
series-corrected
parallel-corrected
Fluorescent lamps (EB – electronic
ballasts)
Mercury and sodium vapour lamps
parallel-compensated
Compact fluorescent lamps (EB)
LED-lamps (< 2 W)
LED-lamps (2 W–8 W)
LED-lamps (> 8 W)
Contact material
Switch output
u
COPY
COPY TIME
SWITCH ->
SWITCH
OBELISK
OVERWRITE OK
PROGRAM.
u
u
RUN OBELISK
CHECK OBELISK
230–240 V AC +10 % / –15 %
50–60 Hz
typ. 4 VA
0,8 W
16 A (at 250 V AC, cos ϕ = 1)
10 A (at 250 V AC, cos ϕ = 0,6)
10 mA/230 V AC
100 mA/12 V AC/DC
IP 20 in accordance with EN
60529
II in accordance with EN
60730-1 subject to designated
installation
–30 °C ... +55 °C
10 years at +20 °C
± 0,25 s/day (25 °C)
4 kV
2
two way switch, contact µ
50 000
2600 W
2600 W
2300 VA
2300 VA
730 W (80 µF)
650 W
730 VA (80 µF)
170 W
30 W
100 W
120 W
AgSnO
2
floating
5