CALIBRATION TAB

1. Changing the 4 and 20 mA set points occurs on the Calibration Tab. The procedure is the same for Level 1, Level 2 and Temperature.
2. Click 'Read' to determine current set point and units.
3. Select units from drop down menu.
4. Change set point. The 4 mA set point is the Zero or Lower Range Value (LRV). The 20 mA set point is the Span or Upper Range Value
(URV).
5. Click 'Write.' Click 'Read' and confirm the new set points are correct.
The Offset field can be used for making adjustments to the optional LCD display, not the current output. This allows the display to be scaled
for local viewing only.
1. Click 'R' to determine current offset
2. Enter offset in same units as set points and click 'W'
3. Click 'R' and validate offset is correct. Display should now be adjusted.

OUTPUT TAB

Output Mapping: allows process variables measured by the level transmitter to be mapped to current loops of level transmitter and HART
variables. Contact Technical Support for questions.
Output Units: The units of measure for level and temperature may be selected using the pull down menus. When changing units, these
selections should be changed on this screen first, prior to changing units on any of the other tabs (Advance Setup or Calibration).
Read: This button sends a single read command to the transmitter and displays the data which the transmitter responds with.