True RMS Digital Multimeter 
With Non‐Contact Voltage Detector and Low Pass Filter 
 
Model MN62 

Advertisement

Table of Contents
loading

Summary of Contents for Extech Instruments MN62

  • Page 1 USER GUIDE      True RMS Digital Multimeter  With Non‐Contact Voltage Detector and Low Pass Filter    Model MN62 ...
  • Page 2 Introduction  Thank you for selecting the Model MN62 True RMS Auto‐ranging Multimeter. This meter measures  AC/DC  Voltage,  AC/DC  Current,  Variable  Frequency  Voltage  (VFC),  Resistance,  Capacitance,  Frequency,  Duty  Cycle  (AC  only),  Diode  Test,  and  Continuity;  a  Non‐Contact  Voltage  Detector  is  also built‐in. This device is shipped fully tested and calibrated and, with proper use, will provide  years of reliable service. Please visit our website (www.extech.com) to check for the latest version  of this User Guide, Product Updates, Product Registration, and Customer Support.    Features   True RMS AC Measurements   Non‐contact Voltage Detector   4000 Count Multifunction LCD Display   Automatic and Manual Ranging  ...
  • Page 3 Safety  The MN62 is designed in compliance with standards such as IEC/EN61010‐1, pollution grade II,  overvoltage CAT III 600V and double insulation standards. Please comply with the instructions  provided in this guide otherwise the protection provided by the instrument may be affected.  This symbol adjacent to another symbol, terminal or operating device indicates  that the operator must refer to an explanation in the Operating Instructions to  avoid personal injury or damage to the meter.  This WARNING symbol indicates a potentially hazardous situation, which if not  WARNING avoided, could result in death or serious injury.  This CAUTION symbol indicates a potentially hazardous situation, which if not  CAUTION avoided, may result damage to the product.  This symbol advises the user that the terminal(s) so marked must not be  600V connected to a circuit point at which the voltage with respect to earth ground  exceeds (in this case) 600V AC rms or DC.  This symbol adjacent to one or more terminals identifies them as being  associated with ranges that may, in normal use, be subjected to particularly  hazardous voltages. For maximum safety, the meter and its test leads should  not be handled when these terminals are energized.  This symbol indicates that a device is protected throughout by double  insulation or reinforced insulation.    PER IEC1010 OVERVOLTAGE INSTALLATION CATEGORY  OVERVOLTAGE CATEGORY I  Equipment  of  OVERVOLTAGE  CATEGORY  I  is  equipment  for  connection  to  circuits  in  which  measures are taken to limit the transient overvoltages to an appropriate low level. ...
  • Page 4   This meter has been designed for safe use, but must be operated with caution. The rules listed below must  be carefully followed for safe operation.    1. NEVER apply voltage or current to the meter that exceeds the specified maximum:  Input Protection Limits Function  Maximum Input V DC or V AC  600VDC/AC rms µA/mA AC/DC  500mA 600V fast acting fuse A AC/DC  10A 600V fast acting fuse Frequency, Resistance, Capacitance, Duty Cycle,  600VDC/AC rms Diode Test, Continuity  2. USE EXTREME CAUTION when working with high voltages.  3. DO NOT measure voltage if the voltage on the "COM" input jack exceeds 600V above earth ground.  4. NEVER connect the meter leads across a voltage source while the function switch is in the current,  resistance, or diode mode. Doing so can damage the meter.  5. ALWAYS discharge filter capacitors in power supplies and disconnect the power when making resistance  or diode tests.  6. ALWAYS turn off the power and disconnect the test leads before opening the covers to replace the fuse  or batteries.  7. NEVER operate the meter unless the back cover and the battery and fuse covers are in place and fastened  securely.  8. NEVER change the measurement function by turning the function dial while testing.  9. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the  equipment may be impaired.   MN62‐en‐GB_V1.1   12/15 ...
  • Page 5: Meter Description

    8. ‘mAµA’ probe input jack  9. COM (‐) input jack  10. Positive (+) input jack  11. SELECT‐Variable Frequency Control button  12. HZ‐% button  13. REL (Relative) button    Note: Tilt stand, test lead holders, and battery/fuse compartment are on rear of unit.    Button Descriptions   RANGE button  The default mode is Auto Range. To manually range, press RANGE to step through the ranges.   Press and hold RANGE to return to Auto Range mode. Auto Range is displayed in Auto mode.  MAX‐MIN button  Press to activate the MAX/MIN recording mode (MAX will appear). The meter will display and  hold the maximum reading. Press again (MIN will appear). The meter will display and hold the  minimum reading. To exit, press and hold MAX‐MIN for 2 seconds.  REL (Relative) button  The displayed value, at the time of the button press, becomes the Reference value with which  subsequent readings are compared. See dedicated Relative mode section.  HOLD and Backlight   button    Short press to freeze displayed reading (H icon is visible). Press again to release reading.  Press and hold to switch backlight ON or OFF.  Hz‐% button  Frequency (Hz) and Duty Cycle (%) modes. Available only in the AC Voltage/Current and  Frequency modes.  SELECT‐VFC button  Short presses select AC or DC for voltage and current measurements.  In AC Voltage VFC mode, press and hold to access VFC (Variable Frequency Control) where a  low pass filter is employed for measuring the voltage of a variable frequency/speed drive.   MN62‐en‐GB_V1.1   12/15 ...
  • Page 6: Display Description

    See units prefix list below  Voltage  See units prefix list below  Amperes (Amps) Current  Farads (Capacitance)  Percent (%) duty cycle (for AC only)  Battery status icon  APO (Auto Power OFF) active   Measurement reading digits  Non‐contact voltage detector (displays EF in reading area)  Auto Range is shown in Auto Range mode  MAX‐MIN memory active  Data Hold active  Continuity test (Resistance)  Diode test  Minus (negative) sign  AC (alternating current) or DC (direct current) mode  VFC (low pass filter) Variable Frequency Control  Measurement unit prefixes  ‐9 n  nano (10 ) (capacitance)  ‐6 µ  micro (10 ) (amps, cap)  ‐3 m  milli (10 ) (volts, amps)    k  kilo (10 ) (ohms)    M  mega (10 ) (ohms)   MN62‐en‐GB_V1.1   12/15 ...
  • Page 7: Auto Power Off (Apo)

    AUTOMATIC and MANUAL Range  The meter defaults to AUTO Range mode when it is switched ON. In this mode the meter  automatically selects the best range for the measurements being made and is generally the best  mode for most measurements. For measurement situations requiring that a range be manually  selected, perform the following:  1. Press the RANGE button. The “AUTO RANGE” display indicator will turn off.  2. Press the RANGE button to step through the available ranges.  3. To exit the Manual Ranging mode and return to Auto ranging, press and hold the RANGE  button for 2 seconds.  MAX/MIN Memory  1. Press the MAX/MIN button to activate the MAX/MIN recording mode. The display icon MAX  will appear. The meter will display and hold the maximum reading and will update only when  a new maximum reading occurs.  2. Press the MAX/MIN button again and the display icon MIN will appear. The meter will  display and hold the minimum reading and will update only when a new minimum reading  occurs.  3. To exit MAX/MIN mode press and hold the MAX/MIN button for 2 seconds.  Relative mode  The relative measurement feature allows the user to make measurements relative to a stored  reference value. A reference voltage, current, etc. can be stored where subsequent  measurements can be made in comparison to that stored reference value. The displayed value is  the difference between the reference value and the measured value.    1. Perform a measurement as described in the operating instructions.  2. Press the REL button to store the reading; the Relative indicator will appear on the display.  3. The display will now indicate the difference between the stored and measured value.  4. Press the REL button to exit the relative mode. The Relative indicator will switch OFF.   MN62‐en‐GB_V1.1   12/15 ...
  • Page 8: Display Backlight

    Display Backlight  Press and hold the    button to turn the backlight ON/OFF. The backlight will automatically turn  off after 30 seconds.  Data Hold  The Data Hold function freezes the reading in the display. Press the HOLD button to switch Data  Hold ON/OFF. When the Data Hold mode is active the display will show the H icon.  DC VOLTAGE MEASUREMENTS   CAUTION:  Do not measure DC voltages if a motor on the circuit is being switched ON or OFF. Large voltage  surges may occur that can damage the meter.  Set the function switch to the V position.   Press the SELECT button to switch to DC if necessary.  Insert the black test lead banana plug into the negative COM jack.  Insert the red test lead banana plug into the positive V jack.  Touch the black test probe tip to the negative side of the circuit.   Touch the red test probe tip to the positive side of the circuit.  Use the RANGE button to manually range the reading. Press and  hold the RANGE button to return to Auto Range Mode. Read the  voltage in the display.     AC VOLTAGE MEASUREMENTS  WARNING:  Risk of Electrocution. The probe tips may not be long enough to contact the live parts inside  some 240V outlets for appliances because the contacts are recessed deep in the outlets. As a result, the  reading may show 0 volts when the outlet actually has voltage on it. Make sure the probe tips are touching  the metal contacts inside the outlet before assuming that no voltage is present.    CAUTION:  Do not measure AC voltages if a motor on the circuit is being switched ON or OFF. Large voltage  surges may occur that can damage the meter.  Set the function switch to the V position.  Press the SELECT button to switch to AC if necessary.  Insert the black test lead banana plug into the negative COM jack.  Insert red test lead banana plug into the positive V jack.  Touch the black test probe tip to the neutral side of the circuit.  Touch the red test probe tip to the “hot” side of the circuit.  Read the voltage in the display.   Use the RANGE button to manually range the reading. Press and  hold the RANGE button to return to Auto Range Mode.   MN62‐en‐GB_V1.1   12/15 ...
  • Page 9 AC VOLTAGE MEASUREMENTS with VFC, Hz, and % Duty Cycle  WARNING:  Risk of Electrocution. The probe tips may not be long enough to contact the live parts inside  some 240V outlets for appliances because the contacts are recessed deep in the outlets. As a result, the  reading may show 0 volts when the outlet actually has voltage on it. Make sure the probe tips are touching  the metal contacts inside the outlet before assuming that no voltage is present.    CAUTION:  Do not measure AC voltages if a motor on the circuit is being switched ON or OFF. Large voltage  surges may occur that can damage the meter.  Set the function switch to the VFC position.   Insert the black test lead banana plug into the negative COM jack.  Insert red test lead banana plug into the positive V jack.  Press and hold the VFC button until the meter beeps and VFC is  briefly displayed. The meter is now applying a low pass filter (Note:  VFC is Variable Frequency Control). Press and hold the VFC button  again to exit the VFC mode (END will briefly display).  Touch the black test probe tip to the neutral side of the circuit.  Touch the red test probe tip to the “hot” side of the circuit.  Read the voltage in the display.   Press the Hz/% button to indicate Hz.  Read the frequency in the display.  Press the Hz/% button again to indicate %.  Read the % duty cycle in the display.  %  Duty  Cycle  Note:  Duty  Cycle  measurements  are  AC  only  for  this  meter.  Measurement  signals must be ‘zero crossing’ and must reach ‐0.7V for the meter to properly display Duty  Cycle %.   MN62‐en‐GB_V1.1   12/15 ...
  • Page 10: Dc Current Measurements

    DC/AC MILLIVOLT MEASUREMENTS   CAUTION:  Do not measure DC/AC voltages if a motor on the circuit is being switched ON or  OFF. Large voltage surges may occur that can damage the meter.  Set the function switch to the mV position.   Insert the black test lead banana plug into the negative COM jack.  Insert the red test lead banana plug into the positive V jack.  Press the SELECT button to select DC or AC millivolts.  Touch the black test probe tip to the negative side of the circuit.   Touch the red test probe tip to the positive side of the circuit.  (Figure at right shows DC measurement only).  Read the voltage in the display.   For AC, press the Hz/% button to indicate Hz.  Read the frequency in the display.  For AC, press the Hz/% button again to indicate %.  Read the % duty cycle in the display.  DC CURRENT MEASUREMENTS  CAUTION:  Do not make 5A current measurements for longer than 30 seconds. Allow 15  minutes between tests. Exceeding 30 seconds may cause damage to the meter and/or the test  leads.  Insert black test lead banana plug into the negative COM  jack.  For current measurements up to 6000µA DC, set the  function switch to the µA position and insert the red test  lead banana plug into the µA/mA jack.  For current measurements up to 600mA DC, set the function  switch to the mA position and insert the red test lead  banana plug into the µA/mA jack.  For current measurements up to 10A DC, set the function  switch to the A position and insert the red test lead banana  plug into the 10A jack.  Press the SELECT button to indicate DC on the display.  Remove power from the circuit under test, then open up the  circuit at the point where you wish to measure current.  Touch the black test probe tip to the negative side of the circuit. Touch the red test probe  tip to the positive side of the circuit.  Apply power to the circuit.  Read the current in the display.    MN62‐en‐GB_V1.1   12/15 ...
  • Page 11: Ac Current (Frequency, Duty Cycle) Measurements

    For current measurements up to 600mA AC, set the  function switch to the mA position and insert the red  test lead banana plug into the µA/mA jack.  For current measurements up to 10A AC, set the  function switch to the A position and insert the red  test lead banana plug into the 10A jack.  Press the SELECT button to indicate “AC” on the  display.  Remove power from the circuit under test, then open  up the circuit at the point where you wish to measure  current.  Touch the black test probe tip to the neutral side of  the circuit.   Touch the red test probe tip to the “hot” side of the circuit.  Apply power to the circuit.  Read the current in the display.  Press the Hz/% button to indicate “Hz”.  Read the frequency in the display.  Momentarily press the Hz/% button again to indicate “%”.  Read the % duty cycle in the display.  Press the Hz/% button to return to the current‐only measurement.    %  Duty  Cycle  Note:  Duty  Cycle  measurements  are  AC  only  for  this  meter.  Measurement    signals must be ‘zero crossing’ and must reach ‐0.7V for the meter to properly display Duty  Cycle %.   MN62‐en‐GB_V1.1   12/15 ...
  • Page 12: Resistance Measurements

     position.  Insert the black test lead banana plug into the negative COM jack.  Insert the red test lead banana plug into the positive Ω jack.  Press the SELECT button to indicate Ω on the display.  Touch the test probe tips across the circuit or part under test. It is  best to disconnect one side of the part under test so the rest of the  circuit will not interfere with the resistance reading.  Read the resistance in the display.  Resistance Measurement Notes  The display shows OL when the measured resistance open‐circuit or  resistance value exceeds maximum range.  When measuring low resistance, a test‐lead measurement error of 0.1 to    will exist. Short the test leads and use the Relative mode to null the test‐lead error.   Check the test leads for loosening or other breakage and verify that the lead resistance is 0.5   or less by shorting the leads and viewing the displayed reading. Replace test leads if necessary.  Several seconds are required for stability when taking high resistance measurements.  Do not input signals > 60VDC or 30VAC.    CONTINUITY CHECK  WARNING: To avoid electric shock, never measure continuity on circuits or wires that have  voltage on them.  Set the function switch to the Ω          position.  Insert the black lead banana plug into the negative COM jack.  Insert the red test lead banana plug into the positive Ω jack.  Press the SELECT button to indicate Ω on the display  Touch the test probe tips to the circuit or wire you wish to check.   If the resistance is > 150Ω there will be a break in the circuit but no  beeper will sound. If the resistance is   10Ω, the beeper signal will  ≤ sound. If the circuit is open, the display will indicate “OL”.  Continuity Measurement Notes   Switch OFF power to any devices on the measurement circuit   Do not input signals > 60VDC or 30VAC   MN62‐en‐GB_V1.1   12/15 ...
  • Page 13: Diode Test

    DIODE TEST  Set the function switch to the Ω          position.  Insert the black test lead banana plug into the negative COM  jack and the red test lead banana plug into the positive V jack.  Press the SELECT button to indicate   and V on the display.  Touch the test probes to the diode under test. Forward voltage  will typically indicate 0.400 to 0.700V. Reverse voltage will  indicate “OL”. Shorted devices will indicate near 0V and an open  device will indicate “OL” in both polarities.    Diode Measurement Notes  Switch OFF power to any devices on the measurement circuit  Do not input signals > 60VDC or 30VAC      CAPACITANCE MEASUREMENTS  WARNING: To avoid electric shock, disconnect power to the unit under test and discharge all  capacitors before taking any capacitance measurements. Remove the batteries and unplug the  line cords.  Set the rotary function switch to the Capacitance symbol position.  Insert the black test lead banana plug into the negative COM jack.  Insert the red test lead banana plug into the positive V jack.  Touch the test leads to the capacitor to be tested.  Read the capacitance value in the display    Capacitance Measurement Notes  The meter will display a fixed reading with no input connected, this is  the internal fixed capacitance; please use the Relative mode to null the  effect of the internal fixed capacitance (especially for low capacitance  measurements).  The display will show OL when the capacitor is short‐circuited or if the  capacitance value exceeds the maximum range of the meter.  High capacity capacitors require a longer time period to stabilize than  lower capacity devices.  To prevent damage to the instrument and personal injury, release all  residual charges to devices under test before taking measurements.       MN62‐en‐GB_V1.1   12/15 ...
  • Page 14: Non-Contact Voltage Detector

    Set the rotary function switch to the Hz/% position.  Insert the black lead banana plug into the negative COM jack and  the red test lead banana plug into the positive Hz jack.  Touch the test probe tips to the circuit under test.  Read the frequency on the display.  Press the Hz/% button to indicate “%”.  Read the % duty cycle in the display.        %  Duty  Cycle  Note: Duty Cycle measurements are AC only for this    meter. Measurement signals must be ‘zero crossing’ and must reach    ‐0.7V for the meter to properly display Duty Cycle %.      Frequency (Electronic) Measurement Note: Do not input signals > 60VDC or 30VAC          NON‐CONTACT VOLTAGE DETECTOR  WARNING: To avoid electric shock, do not use this meter in the Non‐Contact Voltage Detector  mode if the meter does not power up when the function dial is set to the NCV position.  Set the rotary function switch to the NCV position.  Hold the meter top near to a source of AC voltage or  electromagnetic field. The test leads are not necessary in  the NCV mode.  The front LED lamp will light and the beeper will sound  when an AC voltage or electromagnetic field is sensed.  The beeper sound changes with changing intensity of the  detected energy source.  The display shows EF (Electromotive Force) in this mode.       MN62‐en‐GB_V1.1   12/15 ...
  • Page 15: Maintenance

    WARNING: To avoid electric shock, disconnect the test leads from any source of voltage before removing the battery cover. Turn power off and disconnect the test leads from the meter.  Open the rear battery cover (behind the tilt stand) by removing the screw using a Phillips  head screwdriver.  Replace the two (2) 1.5V AA batteries in the battery holder, observing correct polarity.  Put the battery cover back in place. Secure with the screw.    Never dispose of used batteries or rechargeable batteries in household waste.  As consumers, users are legally required to take used batteries to appropriate collection  sites, the retail store where the batteries were purchased, or wherever batteries are sold.  Disposal: Do not dispose of this instrument in household waste. The user is obligated to take  end‐of‐life  devices  to  a  designated  collection  point  for  the  disposal  of  electrical  and  electronic equipment.     WARNING: To avoid electric shock, do not operate the meter until the battery cover is in place  and fastened securely.  NOTE: If the meter does not work properly, check the fuses and batteries to make sure that they  are still good and that they are properly inserted.      MN62‐en‐GB_V1.1   12/15 ...
  • Page 16 FUSE REPLACMENT  WARNING: To avoid electric shock, disconnect the test leads from any source of voltage before  removing the meter cover.  Disconnect the test leads from the meter.  Remove the meter’s protective rubber holster (jacket).  Loosen the center Phillips head screw on the back of the meter while pulling the battery  compartment cover away from the meter. When the screw is loosened sufficiently, the  battery compartment cover can be removed. Refer to diagram below.  Remove the batteries.  Fuse F1 will be visible (directly below the battery compartment); replace fuse F1: FF0.5A H  600V (CE) (ϕ6x32mm).  Remove the remaining two Phillips head screws located on the back of the meter near the  bottom.  Open the meter housing by pulling the two halves of the meter assembly apart.  Fuse F2 will be now be visible (directly below F1); replace fuse F2: F10A H 600V (CE)  (ϕ6x25mm).  When replacing fuses, gently remove the old fuse and install the new fuse into the holder.  Always use a fuse of the proper size and value.  Re‐assemble and secure the meter housing, batteries, and battery cover before attempting  to use the meter.  WARNING: To avoid electric shock, do not operate the meter until the meter housing and  battery compartment cover are fastened securely.   MN62‐en‐GB_V1.1   12/15 ...
  • Page 17: Electrical Specifications

    All AC voltage ranges are specified from 5% of range to 100% of range  Crest Factor: ≤3 at full scale up to 400V, decreasing linearly to ≤1.5 at 600V  DC Current  400.0A  0.1A  4000A  1A  (0.7% reading + 2 digits)  40.00mA  10A  400.0mA  0.1mA 4.000A  (1.0% reading + 3 digits)  10.00A  10mA DCA notes:  Overload protection for A/mA range: F1 fuse (ϕ6x32)mm; FF0.5A H 600V (CE) Overload protection for 10A range: F2 fuse (ϕ6x25)mm F 10A H 600V (CE)  AC Current  400.0A  0.1A     4000A  1A  (1.0% reading + 3 digits)  40.00mA  10A  400.0mA  0.1mA 4.000A  (1.2% reading + 3 digits)  10.00A  10mA ACA notes:  True RMS  Frequency response: 45~1kHz  All AC voltage ranges are specified from 5% of range to 100% of range  Overload protection same as DC Current overload protection (see above)   MN62‐en‐GB_V1.1   12/15 ...
  • Page 18 (Relative) (4.0% reading + 10 digits)  (4.0% reading + 5 digits)  99.99nF~999.9µF 10pF~0.1µF (10% reading)   9.999mF~99.99mF 1µF~10µF Capacitance notes: Overload protection: 600V  For capacitor measurements ≤ 1µF use Relative measurements to ensure measurement  accuracy (0.1% reading + 4 digits)  Frequency  9.999Hz~9.999MHz 0.001Hz~0.001MHz  (electronic)  Duty Cycle  1%~99% 0.1% Not defined   Frequency and Duty Cycle notes: Overload protection 600V  Input range sensitivity:   ≤ 100kHz: 100mVrms  >100kHz: 200mVrms  >1MHz: 500mVrms  5MHz~10MHz: 900mVrms  Duty Cycle %  is only applicable for zero crossing AC measurements ≤ 100kHz  Continuity  Beeper sounds when resistance is ≤ 10. Display resolution: 0.1;  Overload protection: 600V Diode  Open circuit voltage is approx. 3.2V. Silicon PN junction bias ranges 0.5 to 0.8V Resolution: 1mV; Overload protection: 600V    Note: Accuracy specifications consist of two elements:   (% reading) Accuracy of the measurement circuit   (+ digits) Accuracy of the analog to digital converter   MN62‐en‐GB_V1.1   12/15 ...
  • Page 19: General Specifications

        10A range: F2 fuse (ϕ6x25mm) F 10A H 600V (CE) Operating Temperature  0 C to 40 C (32 F to 104 F)  Storage Temperature  ‐10 C to 50 C (14 F to 122 F)    Operating Humidity  ≤ 75% RH for 0~30 C (32~86 F); ≤ 50% RH for 30~40 C (86~104   Operating Altitude  2000m (7000’) maximum  Weight   350g (12.3oz.) includes holster and batteries  Dimensions   175 x 80 x 48.5mm (6.9 x 3.1 x 1.9”) includes holster  Safety  EN61010‐1: CATIII 600V; Pollution Degree 2   Approvals  CE/UL  UL Listed  The UL mark does not indicate that this product has been evaluated for  the accuracy of its readings.    Copyright © 2015 FLIR Systems, Inc.  All rights reserved including the right of reproduction in whole or in part in any form  www.extech.com      MN62‐en‐GB_V1.1   12/15 ...