The negative-sequence instantaneous overcurrent element can be used as an instantaneous function with no intentional
delay or as a definite time function. The element responds to the negative-sequence current fundamental frequency
phasor magnitude (calculated from the phase currents) and applies a positive-sequence restraint for better performance:
a small portion (12.5%) of the positive-sequence current magnitude is subtracted from the negative-sequence current
magnitude when forming the operating quantity.
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence
currents resulting from
System unbalances under heavy load conditions
Transformation errors of current transformers (CTs) during three-phase faults
Fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how the test currents are injected into the relay (single-phase injection:
I
= 0.2917 x I
op
injected
5

5.7.8 Voltage elements

5.7.8.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS
 VOLTAGE ELEMENTS
5-190
NEG SEQ IOC1
EVENTS: Disabled
I
= |I_2| - K x |I_1| where K = 1/8
op
; three-phase injection, opposite rotation: I
Figure 5-95: Negative sequence IOC1 logic
 PHASE
 UNDERVOLTAGE1
 PHASE
 UNDERVOLTAGE3
 PHASE
 OVERVOLTAGE1
 PHASE
 OVERVOLTAGE3
 NEUTRAL OV1
Range: Disabled, Enabled
= I
).
op
injected
See below
See page 5-193
See page 5-194
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Eq. 5-21

Advertisement

Table of Contents
loading

Table of Contents