3.1 System Power/Loop Connections
Stand-alone application, no current loop used
Connection to a PLC/Recorder, separate supply
Transmitter
Loop 2 –
Loop 2 +
System Power Loop 1 –
System Power Loop 1 +
AUX Power –
AUX Power +
Example: Two transmitters connected to PLC/Recorder with separate power supply
System Power Loop 1 –
System Power Loop 1 +
AUX Power –
AUX Power +
Auxiliary Power Note:
Auxiliary power is used ONLY if the flow sensors require more than 1.5 mA of current. This is limited to the following Signet flow sensors:
• 2000, 2507, 2530, 2535, 2540 only if manufactured prior to Jan 1999, 7002 Vortex
• All dual open-collector sensor systems
3.2 Sensor Input Connections
Wiring Tips:
Do not route sensor cable in conduit containing AC power wiring.
Electrical noise may interfere with sensor signal.
Routing sensor cable in grounded metal conduit will help prevent
electrical noise and mechanical damage.
Seal cable entry points to prevent moisture damage.
Only one wire should be inserted into a terminal. Splice double
wires outside the terminal.
Terminals
No Aux Power
Snsr 2 Gnd
16
(SHIELD)
515/3-8510-XX
Snsr 2 IN
15
525
(RED)
Snsr 2 V+
2100
14
(BLACK)
2517
Snsr 1 Gnd
13
(SHIELD)
2536/3-8512-XX
Snsr 1 IN
12
(RED)
2540/2541
Snsr 1 V+
11
7000 Vortex
(BLACK)
8550-3 Flow Transmitter Instructions
Transmitter
Terminals
Loop 2 –
Loop 2 +
System Power Loop 1 –
System Power Loop 1 +
AUX Power –
AUX Power +
PLC or Recorder
+
Channel 2
Terminals
4-20 mA
6
5
Channel 1
4-20 mA
4
+
3
Power
2
Supply
+
1
12–24 VDC
Transmitter 1
Terminals
6
Loop 2 –
Loop 2 +
5
4
3
2
1
Aux Power Required
2000
2507
2530
2535
2540 (mfg prior to Jan 1999)
7002 Vortex
dual open-collector sensor
systems
6
NC
5
NC
Power
4
Supply
3
+
12–24 VDC
2
1
Connection to a PLC with built-in power supply
Transmitter
Terminals
Loop 2 –
Loop 2 +
System Power Loop 1 –
System Power Loop 1 +
AUX Power –
AUX Power +
PLC or Recorder
+
Channel 1
4-20 mA in
+
Channel 2
4-20 mA in
Channel 3
+
4-20 mA in
Channel 4
Transmitter 2
+
4-20 mA in
Power
Supply
+
12–24 VDC
Maximum cable length is 200 ft. for 515/8510-XX,
525, 2517 and any sinusoidal flow signal.
Maximum cable length is 1000 ft. for 2536/
8512-XX, 2540/2541, vortex, and any open-
collector flow signal.
‡ SIGNET
PLC Terminals
+
6
Channel 2
4-20 mA
5
4
+
Channel 1
4-20 mA
3
2
Power
Supply
+
1
12–24 VDC
Internal
PLC Connection
Terminals
6
Loop 2 –
5
Loop 2 +
System Power Loop 1 –
4
System Power Loop 1 +
3
AUX Power –
2
AUX Power +
1
8550-3
Flow
Flow1:
6.25 GPM
B
Flow2:
9.75 GPM
ENTER
A
200 ft. (61 m)
B
200 ft. (61 m)
8550-3
Flow
Flow1:
6.25 GPM
B
Flow2:
9.75 GPM
ENTER
A
1000 ft. (305 m)
B
1000 ft. (305 m)
A
A
page 3 of 8