Panasonic S-200PE2E5 Technical Data & Service Manual page 58

Dc inverter
Table of Contents

Advertisement

1
Reference diagram for snow-proof duct - 1
Space requirements for setting - (1)
The models of U-200PE1E8 / U-250PE1E8 with snow-proof duct
[Obstacle to the rear of unit]
z Top is open:
(1)
Single-unit installation (2) Obstacles on both sides
(3) Multiple-unit installation (2 or more units)
M i n . E
or more
M i n . F
or more
Outdoor unit
U-200PE1E8 / U-250PE1E8
Notes:
1. In cases 2 and 3 the height of the obstacle
must be no taller than the height of the outdoor
unit.
2. The amount of space required for removing
the screw on the rear of the unit.If in case the
sufficient space for maintenance is ensured
on the rear of the outdoor unit, installation is
possible with the space of both sides of not less
than 150mm where marked with * mark.
z Top is blocked by an obstacle:
(Both sides are open)
Outdoor unit
U-200PE1E8 / U-250PE1E8
M i n . B
or more
M i n . C
or more
M i n . E
M i n . E
or more
or more
Unit : mm
A
B
C
D
E
F
150
150 250* 200 250* 150
Min. L
or more
Unit : mm
K
L
500
150
[Obstacle to the front of unit]
z Top is open:
(1)
Single-unit installation
(2) Multiple-unit installation (2 or more units)
Min. I
or more
Outdoor unit
U-200PE1E8 / U-250PE1E8
Note:
The amount of space required for removing the
G
screw on the rear of the unit.
200
If in case the sufficient space for maintenance
is ensured on the rear of the outdoor unit,
installation is possible with the space of both
sides of not less than 150mm where marked with
* mark.
z Top is blocked by an obstacle:
(Both sides are open)
Min. M
or more
Outdoor unit
U-200PE1E8 / U-250PE1E8
1-52
Unit: mm
Min. I
or more
Unit : mm
H
I
J
500
250*
1000
Unit : mm
M
N
500
300

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents