Sensor Temperature Display Function
(displayed regardless of whether unit
is operating or stopped)
The procedure below displays the sensor
temperatures from the remote controller, indoor unit,
and outdoor unit on the remote controller.
<Procedure>
1 Press and hold the
simultaneously for 4 seconds or longer.
2 The unit No. "X-X" (main unit No.), item code "XX"
(sensor address), and servicing monitor "
(sensor temperature) are displayed on the remote
controller LCD display. (See Fig. 7-4 at right.)
3 Press the temperature setting
buttons and select the item code to the address of
the sensor to monitor.
(For the relationships between the sensor
addresses and sensor types, refer to the table of
temperature sensors and addresses at below.)
4 If group control is in effect, press the
button to select the unit to monitor.
Press the temperature setting buttons to select the
item code to change.
5 Press the
button to return to normal remote
controller display.
Indoor unit sensors
02
Intake temp.
03
E1
04
E2
05
E3
06
Discharge temp.
07
Discharge temp. setting
Position of indoor unit
08
electronic control valve
and
buttons
"
/
Unit No.1 Unit No.2 Unit No.3 Unit No.4
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
5
1
Note:
The temperature display appears as "- - - -" for units
that are not connected.
* If monitor mode is engaged while normal operation
is in progress, only the parts of the LCD display
shown in the figure will change. Other parts
continue to display the same information as during
normal operation.
Outdoor unit sensors
2A
4A
6A
2B
4B
6B
2C
4C
6C
2D
4D
6D
2E
4E
6E
2F
4F
6F
30
50
70
31
51
71
32
52
72
33
53
73
34
54
74
35
55
75
36
56
76
37
57
77
38
58
78
39
59
79
3A
5A
7A
3B
5B
7B
3C
5C
7C
3D
5D
7D
3E
5E
7E
3F
5F
7F
40
60
80
41
61
81
42
62
82
7-15
2
CZ-RTC2
4
Fig. 7-4
Discharge temp. 1
Discharge temp. 2
High-pressure sensor temp.
Heat exchanger gas 1
Heat exchanger liquid 1
Heat exchanger gas 2
Heat exchanger liquid 2
Outdoor air temp.
For inspection
CT2
For inspection
For inspection
Discharge temp. 3
CT3
For inspection
For inspection
Heat exchanger gas 3
Heat exchanger liquid 3
Low-pressure sensor temp.
Receiver temp.
Oil 1
Oil 2
Oil 3
For inspection
3
7