Interrupts/diagnostic messages
6.3 Diagnostic alarms
Diagnostic alarm
Supply voltage missing
Mismatch of safety destina-
tion address (F_Dest_Add)
Safety destination address
not valid (F_Dest_Add)
Safety source address not
valid (F_Source_Add)
Safety watchdog time value is
0 ms (F_WD_Time)
Parameter F_SIL exceeds
SIL from specific device ap-
plication
Parameter F_CRC_Length
does not match the generat-
ed values
Version of F-parameter set
incorrectly
CRC1 fault
Save iParameter watchdog
time exceeded
Restore iParameter watchdog
time exceeded
Inconsistent iParameters
(iParCRC error)
F_Block_ID not supported
Transmission error: Incon-
sistent data (CRC error)
Transmission error: Timeout
(watchdog time 1 or 2 ex-
pired)
52
Fault
code
17
Missing or insufficient supply voltage L+
D
64
The firmware of the F-module has detected
D
a different F-destination address.
65
The firmware of the F-module has detected
D
an illegal different F-destination address.
66
The firmware of the F-module has detected
D
a different F-source address.
67
The firmware of the F-module has detected
D
an invalid watchdog time.
68
The firmware of the F-module has detected
D
a discrepancy between the SIL setting of
the communication and the application.
69
The firmware of the F-module has detected
D
a discrepancy in the CRC length.
70
The firmware of the F-module has detected
D
an incorrect F_Par_Version or an invalid
F_Block_ID.
71
The firmware of the F-module has detected
D
inconsistent F-parameters.
73
iPar server does not respond to "save IPar"
D
within 4.4 minutes.
74
iPar server does not respond to "restore
D
IPar" within 4.4 minutes.
75
The firmware of the F-module has detected
D
inconsistent iParameters.
76
The firmware of the F-module has detected
D
an incorrect F_block_ID.
77
The firmware of the F-module has detected
D
a CRC error.
Possible causes:
The communication between the F-CPU
and F-module is disturbed.
Impermissibly high electromagnetic
interference is present.
An error occurred in the sign-of-life
monitoring.
78
The firmware of the F-module has detected
D
a timeout.
Possible causes:
The F-monitoring time is set incorrectly.
A bus fault is present.
Meaning
Digital input module F-DI 16x24VDC (6ES7526-1BH00-0AB0)
Remedy
Check supply voltage L+ at the
front connector
Check the front connector
Check the parameter assignment
of the PROFIsafe driver and the
PROFIsafe address assigned to
the F-module.
Assign the PROFIsafe address to
the F-module (again).
Check the parameter assignment of
the iPar server.
Check the parameter assignment of
the iPar server.
Check the parameter assignment.
Check the parameter assignment of
the PROFIsafe driver.
Check the communication con-
nection between the F-module
and F-CPU.
Eliminate the electromagnetic
interference.
Check the parameter assign-
ment.
Ensure that communication is
functioning correctly.
Manual, 01/2016, A5E03858068-AA