Interrupts/diagnostic messages
6.1 Status and error displays
RUN and ERROR LEDs
Table 6- 1
RUN and ERROR status and error displays
LED
RUN
ERROR
Off
Off
Flashing
Off
On
Off
Off
Flashing
On
Flashing
Flashing
Flashing
/
Alternately flashing
PWR LED
Table 6- 2
PWR LED
48
Meaning
Missing or insufficient voltage on the backplane
bus
Module starts up and flashes up to the valid
parameter assignment.
Module parameters are assigned and module
addressed.
Firmware is being updated.
Indicates diagnostic interrupts:
Module fault (for example, supply voltage
•
too high)
Channel fault (for example, frequency too
•
high).
PROFIsafe communication error
•
Operation in S7-1500 F-CPUs: At least one
channel is waiting for user acknowledgment.
Hardware defective.
Operation in S7-1500 F-CPUs: The F-
•
module expects user acknowledgment after
a module error.
Operation in S7-300/400 F-CPUs: At least
•
one channel is waiting for user acknowl-
edgment.
PWR status display
Meaning
Supply voltage L+ missing
Off
Supply voltage L+ available
On
Switch on the CPU and/or the system pow-
•
er supply modules.
Check whether the module is correctly
•
plugged into the U-connector.
Check whether too many modules are
•
plugged in.
---
Evaluate the diagnostics and eliminate or
acknowledge the error. It may be necessary to
remove and re-insert the module.
Replace the module.
Acknowledge the error (see manual SIMATIC
Safety - Configuring and Programming
(http://support.automation.siemens.com/WW/vi
ew/en/54110126)).
Digital input module F-DI 16x24VDC (6ES7526-1BH00-0AB0)
Manual, 01/2016, A5E03858068-AA
Remedy