Install Liquid-Line Filter Drier Indoor; Refrigerant Tubing Connection Outdoor; Sweat Connections; Deep Vacuum Method - Carrier 25HNA6 Installation Instruction

Infinity series heat pump with puron refrigerant 2 to 5 nominal tons (sizes 24 to 60)
Hide thumbs Also See for 25HNA6:
Table of Contents

Advertisement

Install
Liquid-Line
Filter
Drier
Indoor
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5-in. (127 ram) liquid tube to the indoor
coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5-in. (127 ram) liquid
tube. Flow
arrow must point towards indoor
coil.
4. Connect
and braze liquid refrigerant
tube to the filter drier.
I
UNIT
DAMAGE
HAZARD
I
I
Failure
to follow
this caution
may result in equipment
damage
or improper
operation,
Installation
of filter
drier
in liquid
line is required,
and indoor coil are now ready for leak testing. This check should
include all field and factory joints,
Evacuate
Refrigerant
Tubing
and Indoor
Coil
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation,
Never use the system compressor as a vacuum pump.
Refrigerant
tubes
and indoor
coil should
be evacuated
using
the
recommended
deep vacuum
method
of 500 nficrons.
The alternate
triple
evacuation
method
may be used.
See Service
Manual
for
triple
evacuation
method.
Always
break
a vacuum
with
dry
nitrogen.
Deep
Vacuum
Method
The
deep
vacuum
method
requires
a vacuum
pump
capable
of
pulling
a vacuum
of 500 nficrons
and a vacuum
gauge capable
of
accurately
measuring
this vacuum
depth. The deep vacuum
method
is the most
positive
way of assuring
a system
is free of air and
liquid
water. (See Fig. 4)
A05227
Fig. 3 - Liquid-Line
Filter Drier
Refrigerant Tubing connection Outdoor
Connect
vapor tube to fitting on outdoor
unit vapor service valves
(see Table 1).
Install Adapter Tube
1. Remove
plastic
retainer
holding
outdoor
piston
in liquid
service valve.
2. Check
outdoor
piston
size with matching
number
listed on
unit rating plate.
3. Locate plastic bag taped to unit containing
adapter
tube.
4. Remove
Teflon®
washer
from
bag and install on open
end of liquid service valve.
5. Remove
adapter
tube from bag and connect
threaded
nut to
liquid
service valve.
Tighten
nut finger tight and then with
wrench
tighten
an additional
1/2 turn (15 ft-lb).
DO NOT OVERTIGHTEN!
Sweat
Connections
[]NIT
DAMAGE
HAZARD
Failure to follow this caution may result in equipment
damage or improper operation,
• Use a brazing shield
• Wrap service valves with wet cloth or heat sink material.
Use refrigerant
grade tubing.
Service valves are closed from factory
and ready
for brazing.
After wrapping
service
valve
with
a wet
cloth,
braze
sweat
connections
using
industry
accepted
methods
and materials.
Consult
local code requirements.
Refrigerant
tubing
ffJ
O
tr"
O
m
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
1
2
3
4
5
6
MINUTES
Fig. 4 - Deep Vacuum
Graph
A95424
Final
Tubing
Check
IMPORTANT:
Check to be certain factory
tubing
on both indoor
and outdoor
unit has not shifted
during
shipment.
Ensure
tubes are
not
rubbing
against
each
other
or any sheet
metal.
Pay
close
attention
to feeder tubes,
making
sure wire ties on feeder
tubes are
secure and tight.
Make Electrical
Connections
ELECTRICAL
SHOCK
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death.
Do not supply power
to unit with compressor
ternfinal box
cover removed.
Be sure field wiring
complies
with local and national
fire, safety,
and electrical
codes,
and voltage
to system
is within
linfits shown
on unit rating plate. Contact
local power
company
for correction
of
improper
voltage.
See unit rating
plate
for recommended
circuit
protection
device.

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

25hna9

Table of Contents