Failed Thermistor Default Operation; Outdoor Air Thermistor (Oat) Attachment; Outdoor Coil Thermistor (Oct) Attachment - Carrier 25HNA6 Installation Instruction

Infinity series heat pump with puron refrigerant 2 to 5 nominal tons (sizes 24 to 60)
Hide thumbs Also See for 25HNA6:
Table of Contents

Advertisement

Failed
Thermistor
Default
Operation
Factory
defaults
have
been
provided
in the event
of failure
of
outdoor
air thermistor
(OAT)
and/or
outdoor
coil
thermistor
(OCT).
If the OAT sensor
should
fail, low
ambient
cooling
will not be
allowed
and the one-minute
outdoor
fan off delay will not occur.
Defrost will be initiated
based on coil temperature
and time.
If the OCT
sensor
should
fail, low ambient
cooling
will not be
allowed.
Defrost
will occur
at each time interval
during
heating
operation,
but will terminate
after 5 minutes.
OAT Thermistor
must be locked in
place with spherical
nib end facing to-
wards the front of the control box
\\
If there is a thermistor
out of range error, defrost
will occur
at each
time
interval
during
heating
operation,
but will terminate
after 5
minutes.
Count
the
number
of short
and
long
flashes
to determine
the
appropriate
flash code.
Table 6 gives possible
causes
and actions
related
to each error.
/
/
/
/
/
/
/
/
/
/
....
OCT Thermistor
must be secured
tight on stub tube.
Fig. 9 - Outdoor
Coil Thermistor
(OCT)
Attachment
Table 5 - Two-Stage
Compressor
Resistances
(Winding
Resistance
at 70 ° F_+ 20 °F / 21 ° C_+ 11 ° C)
25HNA624
25HNA636
25HNA648
2.74
1.98
1.55
0.80
0.75
0.48
Winding
25HNA660
Start
(S-C)
0.74
Run (R-C)
0.36
Winding
25HNA924
25HNA936
25HNA948
25HNA960
Start
(S-C)
1.40
1.29
1.52
0.60
Run
(R-C)
1.32
0.89
0.64
0.49
13