Unloader Test Procedure; Temperature Thermistors; Thermistor Sensor Comparison - Carrier 25HNA6 Installation Instruction

Infinity series heat pump with puron refrigerant 2 to 5 nominal tons (sizes 24 to 60)
Hide thumbs Also See for 25HNA6:
Table of Contents

Advertisement

continues, the control will energize the compressor contactor every
15 minutes. If the thermal protector closes, (at the next 15 minute
interval check) the unit will resume operation.
If the thermal cutout trips for three consecutive cycles, then unit
operation is locked out for 4 hours and the appropriate fault code is
displayed.
Low or High Contactor
Open
(25HNA6
models)
/ No
230V at Compressor
Contactor
(25HNA9
models)
If the compressor
voltage is not sensed when the compressor
should be starting, the appropriate contactor may be stuck open or
there is a wiring error. The control will flash the appropriate fault
code. Check the contactor and control box wiring.
25HNA6
Models
Only - Compressor
Start Detection
on Models
with Bristol
Compressors
Only
In low stage, if the specified start voltage at VR terminal is not
achieved, the start relay is de-energized
after 1 second and the
control will flash the appropriate fault code.
In high stage, if the specified start voltage at VS terminal is not
achieved, the start relay is de-energized
after 1 second and the
control will flash the appropriate fault code.
If the specified start voltage is not achieved for 3 consecutive low
stage starts, low stage operation is locked out for 30 minutes. If the
specified start voltage is not achieved for 3 consecutive high stage
starts, high stage operation
is locked out for 30 minutes. The
control will flash the appropriate fault code.
Troubleshooting
25HNA6
units for proper
switching
between
low & high sta_es
Check the suction and liquid pressures at the service valves.
Suction pressure should be reduced by 5-10%
when switching
from low to high capacity. There should be a 10-20% increase in
liquid pressure when
switching
from
low to high capacity.
Compressor current should increase 100-250%
when switching
from low to high stage.
Troubleshooting
25HNA9
units for proper
switching
between
low & high sta_es
Check the suction pressures at the service valves.
Suction pressure
should be reduced by 3-10% when switching from low to high
capacity.
NOTE:
The liquid pressures are very similar between low and
high stage operation, so liquid pressure should not be used for
troubleshooting.
Compressor current should increase 20-45% when switching from
low to high stage.
The compressor solenoid when energized in
high stage, should measure 24vac.
When the compressor
is operating
in low stage the 24v DC
compressor solenoid coil is de-energized.
When the compressor is
operating in high stage, the 24v DC solenoid coil is energized. The
solenoid plug harness that is connected to the compressor HAS an
internal rectifier that converts the 24v DC signal to 24v AC. DO
NOT
INSTALL
A
PLUG
WITHOUT
AN
INTERNAL
RECTIFIER.
Unloader
Test Procedure
The unloader is the compressor internal mechanism, controlled by
the DC solenoid, that modulates between high and low stage. If it
is suspected
that the unloader
is not working,
the following
methods may be used to verify operation.
1. Operate the system and measure compressor
amperage.
Cycle the unloader on and off at 30 second plus intervals at
the UI (from low to high stage and back to low stage). Wait
5 seconds after staging to high before taking a reading. The
compressor amperage should go up or down at least 20 per-
cent.
2. If the expected result is not achieved, remove the solenoid
plug from the compressor and with the unit running and the
UI calling for high stage, test the voltage output at the plug
with a DC voltmeter. The reading should be 24 volts DC.
3. If the correct DC voltage is at the control circuit molded
plug, measure the compressor unloader coil resistance. The
resistance should be 32 to 60 ohms depending
on com-
pressor temperature.
If the coil resistance is infinity, nmch
lower than 32 ohms, or is grounded, the compressor nmst
be replaced.
Temperature
Thermistors
Thermistors are electronic devices which sense temperature. As the
temperature increases, the resistance decreases.
Thermistors are
used to sense outdoor air (OAT) and coil temperature (OCT).
Refer to Fig. 7 for resistance values versus temperature.
THERMISTOR
CURVE
9o1 _
r
]
r
q
|
_
I
I
I
I
I
|
701
t
,
t
,
1
6o4 'v4
L
I
_
I
4
U 5°1
t
I
t
I
1
z 404
_\
I
I
J
_< /
",.
I
i
i
i
/
co 301
m
_
I
t
I
1
/
i
/
10 t
_
t
_
1
0
20
40
60
80
100
120
(-17.77)
(-6.67)
(4.44)
(15.56)
(26.67)
(37.78)
(48.89)
TEMPERATURE
°F (°C)
A08054
Fig. 7 - Resistance Values Versus Temperature
If the outdoor
air or coil thermistor
should
fail, the control
will
flash the appropriate
fault code. (See Table 60
IMPORTANT:
The
outdoor
air thermistor
and
coil
thermistor
should
be factory mounted
in the final locations.
Check
to ensure
thermistors
are mounted
properly
per Fig. 8 and Fig. 9.
Thermistor
Sensor
Comparison
The control
continuously
monitors
and compares
the outdoor
air
temperature
sensor
and outdoor
coil temperature
sensor
to ensure
proper
operating
conditions,
The comparison
is:
• In cooling
if the outdoor
air sensor indicates
-> 10°F
(->5.6 o C) warmer
than the coil sensor (or) the outdoor
air sensor
indicates
-> 20 °F (-> 11 oC) cooler than the coil sensor,
the
sensors
are out of range.
• In heating
if the outdoor
air sensor indicates
->35 °F (-> 19.4 ° C)
warmer
than the coil sensor (or) the outdoor
air sensor indicates
-> 10°F (-> 5.6°C)
cooler than the coil sensor,
the sensors
are out
of range.
If the sensors
are out of range, the control will flash the appropriate
fault code as shown
in Table 6.
The thermistor
comparison
is not performed
during
low ambient
cooling
or defrost operation,
12

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

25hna9

Table of Contents