Download Print this page

GE AF-600 Installation And Start-Up Instructions Manual page 6

Advertisement

CONTROL WIRING
(120 VAC )
All field wiring shall have a minimum insulation rating of 75 C (167 F).
Size wire according to local and national codes.
All control wiring must be routed away from power wiring. If control
wiring is routed parallel to signal wiring (24 Vdc or less), isolation of the
signal wiring must be maintained. A minimum of four (4) inches is needed
to adequately separate signal and control wiring. If signal wire is UL
recognized shielded cable, separation can be minimized to a one (1) inch
separation.
AF-600 Redundant Drive Panels require no additional control wiring to
operate properly. Additional control interfacing to your control panel can
be accomplished through the panel mounted customer terminal board
"CTB1". Please reference the appropriate wiring diagram. Torque values
for connecting to "CTB1" are located in the Appendices.
SIGNAL WIRING
(24 VDC or less)
All field wiring shall have a minimum insulation rating of 75 C (167 F).
Size wire according to local and national codes.
All field signal wiring must be twisted and shielded. All shields must be
grounded at one point ONLY. It is recommended to terminate the shield
drains at the signal's source. Avoid routing signal wiring with power
wiring. If signal wiring is routed with control wiring a minimum separation
of one (1) inch is required.
DEH40632
CAUTION: Do not connect power supply voltage greater than panel
rated voltage, or damage will occur to equipment.
WARNING: Never connect or disconnect input wiring with voltage
applied, a serious or fatal injury may result.
WARNING: Never connect or disconnect output wiring with
voltage applied, a serious or fatal injury may result.
6
AN 12-1007, Rev.03, 04/04/2012

Hide quick links:

Advertisement

loading