Quick Start Guide
D103214X012
Table 6. DLC3010 Digital Level Controller Specifications (continued)
Electromagnetic Compatibility
Meets EN 61326‐1:2013 and EN 61326‐2‐3:2006
Immunity—Industrial locations per Table 2 of
EN 61326‐1 and Table AA.2 of EN 61326‐2‐3.
Performance is shown in table 7 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Supply Requirements (See figure 10)
12 to 30 volts DC
; 22.5 mA
Instrument has reverse polarity protection.
A minimum compliance voltage of 17.75 is required
to guarantee HART communication.
Compensation
Transducer compensation: for ambient temperature
Density parameter compensation: for process
temperature (requires user‐supplied tables)
Manual compensation: for torque tube rate at target
process temperature is possible
Digital Monitors
Linked to jumper‐selected Hi (factory default) or Lo
analog alarm signal:
Torque tube position transducer: Drive monitor and
signal reasonableness monitor
User‐configurable alarms: Hi‐Hi and Lo‐Lo Limit
process alarms
HART‐readable only:
RTD signal reasonableness monitor: When RTD
installed
Processor free‐time monitor.
Writes‐remaining in Non Volatile Memory monitor.
User‐configurable alarms: Hi and Lo limit process
alarms, Hi and Lo limit process temperature alarms,
and Hi and Lo limit electronics temperature alarms
Diagnostics
Output loop current diagnostic.
LCD meter diagnostic.
Spot specific gravity measurement in level mode: used
to update specific gravity parameter to improve
process measurement
Digital signal‐tracing capability: by review of
"troubleshooting variables", and
Basic trending capability for PV, TV and SV.
LCD Meter Indications
LCD meter indicates analog output on a percent scale
bar graph. The meter also can be configured to
display:
Process variable in engineering units only.
Percent range only.
Percent range alternating with process variable or
Process variable, alternating with process temperature
(and degrees of pilot shaft rotation).
Electrical Classification
Pollution Degree IV, Overvoltage Category II per IEC
61010 clause 5.4.2 d
Hazardous Area:
CSA— Intrinsically Safe, Explosion‐proof,
Division 2, Dust Ignition‐proof
FM— Intrinsically Safe, Explosion‐proof,
Non‐incendive, Dust Ignition‐proof
ATEX— Intrinsically Safe, Type n, Flameproof
IECEx— Intrinsically Safe, Type n, Flameproof
Refer to Hazardous Area Approvals and Special
Instructions for "Safe Use" and Installations in
Hazardous Locations in the Installation section,
starting on page 5, for additional approvals
information.
Electrical Housing:
CSA— Type 4X
FM— NEMA 4X
ATEX— IP66
IECEx— IP66
Other Classifications/Certifications
CUTR— Customs Union Technical Regulations (Russia,
Kazakhstan, Belarus, and Armenia)
INMETRO— National Institute of Metrology,
Standardization, and Industrial Quality (Brazil)
KGS— Korea Gas Safety Corporation (South Korea)
NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of
Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
TIIS— Technology Institution of Industrial Safety
(Japan)
Contact your
Emerson Process Management sales
office
for classification/certification specific
information
-continued-