CHAPTER 1 Installation Data

1.3.6 Installation Specifications (PRIMEQUEST 2800B2)

Dimensions
Width
[mm (in.)]
Depth (*1)
Length
Mass [kg (lb)] (*2)
Conditions for
Max. calorific value
air conditioner
[kJ/h (BTU/h)]
Displacement
[m3/min (ft
(*3)
Temperature and
Humidity
conditions (*4)
Noise [dB] (*7, *8)
Acoustic power level [B] (*8)
Permissible
Vibration [m/s
(gal)]
Permissible dust level [mg/m
Power supply
Input voltage and source resultant pulse number
conditions
Frequency and fluctuating Range
Max power
consumption /
apparent power
Power factor (*10)
Inrush current [A] [Rush hours] (*11)
Leak current [mA] (*12)
*1: Dimensions without protrusions
*2: Numeric value when each optional device is mounted for maximum number of options.
However, rail for mounting rack (5.7kg) and cable type are not included.
Mass as per the installation configuration can be calculated using formula as shown below.
Device mass = 77 + (9.6 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg]
A = Number of mounted SB (Minimum 1 to Maximum 4)
B= Number of mounted IOU (Minimum 1 to Maximum 4)
C= Number of mounted PSU (Minimum 2 to Maximum 6)
D= Number of mounted DU (Minimum 0 to Maximum 2)
*3: There are cases when device is overloaded or when abnormality is detected, FAN rotates at high-speed
even if recommended environmental temperature is used.
*4: Protect from condensation.
*5: Temperature condition changes according to the installation location above sea level.
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C
(41 to 95°F)
For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to
33°C (41 to 91.4°F)
For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to
31°C (41 to 87.8°F)
For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to
29°C (41 to 84.2°F)
Error of + 100m in the sea level settings of the location of installation is permissible.

TABLE 1.7 Installation Specifications (PRIMEQUEST 2800B2)

Items
Interruptible power source
High efficiency power supply (*13)
Recommended environmental
3
/min)]
temperature
Max.
At the time
of operation
Downtime
(*6)
At the time of operation (Including
2
standby)
Downtime (*9)
At the time
of operation
Downtime
Temperature [°C (°F)]
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]
Temperature [°C (°F)]
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]
3
]
Interruptible power
source (*13)
High efficiency power
supply (*13)
19
Contents
445(17.52)
782(30.79)
438(17.25) 10U
143(315)
19,872(18,835)
19,224(18,221)
12(424)
28(989)
(*5)
20 to 80
29 (84.2)
0 to 50 (32 to 122)
8 to 80
29 (84.2)
60
7.8
4.0 (400) (Composite seismic
wave)
10.0 (1000) (Composite
seismic wave)
0.15
200 to 240 VAC±10 %
50/60 Hz + 2/-4%
5.52 kW/5.69 kVA
5.34 kW/5.51 kVA
0.084 kW
0.95 or more
20 or less
6.9 or less
CA92344-0535-06