Installation Specifications (Primequest 2800E2); Table 1.6 Installation Specifications (Primequest 2800E2) - Fujitsu PRIMEQUEST 2000 Series Hardware Installation Manual

Hide thumbs Also See for PRIMEQUEST 2000 Series:
Table of Contents

Advertisement

CHAPTER 1 Installation Data

1.3.5 Installation Specifications (PRIMEQUEST 2800E2)

Dimensions
Width
[mm (in.)]
Depth (*1)
Length
Mass [kg (lb)] (*2)
Conditions for
Max. calorific
air conditioner
value
[kJ/h (BTU/h)]
Displacement
[m3/min (ft
(*3)
Temperature and
Humidity
conditions (*4)
Noise [dB] (*7, *8)
Acoustic power level [B] (*8)
Permissible
Vibration [m/s
(gal)]
Permissible dust level [mg/m
Power supply
Input voltage and source resultant pulse number
conditions
Frequency and fluctuating Range
Max power
consumption /
apparent power
Power factor (*10)
Inrush current [A] [Rush hours] (*11)
Leak current [mA] (*12)
*1: Dimensions without protrusions (832 mm (32.76in) including front cover)
*2: Numeric value when each optional device is mounted for maximum number of options.
However, rail for mounting rack (5.7kg) and cable type are not included.
Mass as per the installation configuration can be calculated using formula as shown below.
Device mass = 78 + (11.1 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg]
A = Number of mounted SB/Memory Scale-up Board (Minimum 1 to Maximum 4)
B= Number of mounted IOU (Minimum 1 to Maximum 4)
C= Number of mounted PSU (Minimum 2 to Maximum 6)
D= Number of mounted DU (Minimum 0 to Maximum 2)*3: There are cases when device is overloaded or
when abnormality is detected, FAN rotates at high-speed even if recommended environmental
temperature is used.
*4: Protect from condensation.
*5: Temperature condition changes according to the installation location above sea level.
For 0 to 1000 m (0 to 3281 ft) above sea level, temperature range at the time of installation: 5 to 35°C
(41 to 95°F)
For 1000 to 1500 m (3281 to 4921 ft) above sea level, temperature range at the time of installation: 5 to
33°C (41 to 91.4°F)
For 1500 to 2000 m (4921 to 6562 ft) above sea level, temperature range at the time of installation: 5 to
31°C (41 to 87.8°F)

TABLE 1.6 Installation Specifications (PRIMEQUEST 2800E2)

Items
Interruptible power source
High efficiency power supply (*13)
Recommended environmental
3
/min)]
temperature
Max.
At the time
of operation
Downtime
(*6)
At the time of operation (Including
2
standby)
Downtime (*9)
At the time
of operation
Downtime
Temperature [°C (°F)]
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]
Temperature [°C (°F)]
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]
3
]
Interruptible power
source (*13)
High efficiency power
supply (*13)
17
Contents
445(17.52)
782(30.79)
438(17.25) 10U
150(331)
20,340(19,278)
19,692(18,664)
12(424)
28(989)
(*5)
20 to 80
29 (84.2)
0 to 50 (32 to 122)
8 to 80
29 (84.2)
60
7.8
4.0 (400) (Composite seismic
wave)
10.0 (1000) (Composite
seismic wave)
0.15
200 to 240 VAC±10 %
50/60 Hz + 2/-4%
5.65 kW/5.82 kVA
5.47 kW/5.64 kVA
0.084 kW
0.95 or more
20 or less
6.9 or less
CA92344-0535-06