MTU 12 V 4000 L62FB Operating Instructions Manual page 62

Table of Contents

Advertisement

112509 – HIHI T-Exhaust A9
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112510 – HIHI T-Exhaust A10
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112511 – HIHI T-Exhaust B1
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112512 – HIHI T-Exhaust B2
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112513 – HIHI T-Exhaust B3
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
62 | Troubleshooting | MS150098/02E 2016-11
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 140).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 140).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 140).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 140).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 140).
3. Check valve drive (exhaust valves do not close).