Cabinet Installation; Vent Installation - Williams 1753012 Owner's Manual

High efficiency direct-vent wall furnace
Table of Contents

Advertisement

Installation
Venting
Exhaust Piping and Termination (Figure 13-21)
Up to 50 Feet of equivalent vent length may be used. Use
Schedule 40 Standard Wall 2" PVC meeting ASTM Standard
D1784. For Canada, ULC S636 approved duct must be used.
Use a 45° elbow as the vent termination for the exhaust pipe,
vent terminations are not counted towards the overall vent
length.
FIGURE 13
FIGURE 14
Top prevent the flue pipe from being pushed into the wall, use
a hose clamp to hold the PVC pipe in place per Fig. 14.
FIGURE 15