NATURAL GAS CONVERSION
Natural gas conversion must be performed only by your natural gas provider or service
company.
1. Disconnect the regulator hose from the gas valve. See Figure 8.
2. Disconnect the gas tube from the orifice elbow. Remove the two M4 nuts and remove the
orifice holder. Replace the propane orifice with the natural gas orifice from the kit and
reinstall the orifice holder. Apply a solution of soapy water to all connections to check for
leaks. If soap bubbles continue to form, the connection has a leak. If a leak is found, close
the main valve and tighten all connections. NEVER USE A FLAME TO CHECK FOR
LEAKS.
3. Stick the conversion label on the rating plate as shown in Figure 9.
Serial Number
CAUTION: The gas pressure regulator provided with this appliance must be used. .
This appliance has been converted to use Natural Gas.
Input 30,000 Btu/hr.
Max Gas Supply Pressure 7 inch water column(1.74 kPa) Min Gas Supply Pressure 5
inch water column (1.24 kPa)
FOR OUTDOOR USE ONLY. If stored indoors, detach and leave cylinder outdoors.
Oct-01-2014
Figure 8
Metal Rating Plate
Model Number:
Figure 9
8
98300
CONVERSION LABEL