Table 59. Three-phase power and energy (PEMMXU)
Characteristic
Operation accuracy
Suppression of harmonics
Table 60. RTD/mA measurement (XRGGIO130)
Description
RTD inputs
Supported RTD
sensors
Supported resistance
range
Maximum lead
resistance (three-
wire measurement)
Isolation
Response time
RTD/resistance
sensing current
Operation accuracy
mA inputs
Supported current
range
Current input
impedance
Operation accuracy
Table 61. Frequency measurement (FMMXU)
Characteristic
Operation accuracy
Value
At all three currents in range 0.10...1.20 x I
At all three voltages in range 0.50...1.15 x U
At the frequency f
n
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71
±1.5% for power (S, P and Q)
±0.015 for power factor
±1.5% for energy
DFT: -50 dB at f = n x f
Value
100 Ω platinum
TCR 0.00385 (DIN 43760)
250 Ω platinum
TCR 0.00385
100 Ω nickel
TCR 0.00618 (DIN 43760)
120 Ω nickel
TCR 0.00618
250 Ω nickel
TCR 0.00618
10 Ω copper
TCR 0.00427
0...2 kΩ
25 Ω per lead
2 kV (inputs to protective earth)
<4 s
Maximum 0.33 mA rms
Resistance
Temperature
± 2.0% or ±1 Ω
±1°C
10 Ω copper: ±2°C
0...20 mA
44 Ω ± 0.1%
±0.5% or ±0.01 mA
Value
±10 mHz
(in measurement range 35 - 75 Hz)
1MRS757058 D
n
n
±1 Hz
, where n = 2, 3, 4, 5,...
n