Three-Phase Overvoltage Protection (Phptov) Main Settings; Three Phase Undervoltage Protection (Phptuv); Three-Phase Undervoltage Protection (Phptuv) Main Settings - ABB REU615 Product Manual

Relion 615 series voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

ABB
Voltage Protection and Control
REU615
Product version: 4.0
Table 31. Three-phase overvoltage protection (PHPTOV) main settings
Parameter
Start value
Time multiplier
Operate delay time
1)
Operating curve type
1)
For further reference please refer to the Operating characteristics table
Table 32. Three phase undervoltage protection (PHPTUV)
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
Start value = 1.0 x U
1)
, Voltage before fault = 1.1 x U
n
phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Minimum
Start value = 0.50, Start value multiples in range of 0.90 to 0.20
Table 33. Three-phase undervoltage protection (PHPTUV) main settings
Parameter
Start value
Time multiplier
Operate delay time
Operating curve type
1)
1)
For further reference please refer to the Operating characteristics table
Function
PHPTOV
PHPTOV
PHPTOV
PHPTOV
Start value
U
= 0.9 x set
Fault
, f
= 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random
n
n
Function
PHPTUV
PHPTUV
PHPTUV
PHPTUV
Value (Range)
0.05...1.60 x U
n
0.05...15.00
40...300000 ms
Definite or inverse time
Curve type: 5, 15, 17, 18, 19, 20
Value
Depending on the frequency of the voltage measured: fn
±2 Hz
±1.5% of the set value or ±0.002 x U
Minimum
Typical
62 ms
64 ms
< 40 ms
Relative hysteresis
Depends on the set
< 35 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
DFT: -50 dB at f = n x f
, where n = 2, 3, 4, 5,...
n
Value (Range)
0.05...1.20 x U
n
0.05...15.00
60...300000 ms
Definite or inverse time
Curve type: 5, 15, 21, 22, 23
1MRS757058 D
Step
0.01
0.01
10
n
Maximum
66 ms
3)
Step
0.01
0.01
10
29