Disassembly And Assembly Of Compressor - Gree GMV series Service Manual

Dc inverter vrf plus water heater solution
Hide thumbs Also See for GMV series:
Table of Contents

Advertisement

Dc Inverter VRF plus Water Heater Solution Service Manual

Disassembly and Assembly of Compressor

Remarks : Make sure there isn't any refrigerant in pipe system and the power supply is cut off before removal
of the compressor..
Step
1 . Disconnect the electrical
source wire
2.Take down the compressor
from the bottom pan.
3.Fix the new compressor on
to the bottom pan
4. Connect the compressor
with system pipes.
5.Renew the electrical source
wire of compressor
6.Renew the electrical heating
belt
and
exhausting
temperature sensor
7.Check if the compressor
rotates in reverse and if
lubricant have leaked.
Illustration
SERVICING
Handling Instruction
Relax the screws with the
screwdriver.
Draw out the electrical source
wire
Note:Earmark the colour of wire
corresponding to the terminal
when Removing the wire , the
mistakes can be avoided when
renewing the wire connection.
① Disassemble the bolts of
cpmpressor
②Remove the compressor from
chassis.
①Position accurately the new
compressor.
②Screw up nuts.
① Weld the pipeline which
connects
compressor(
discharge
pipe,suction pipe,oil equalized
pipe).
with
270