Dc Inverter VRF plus Water Heater Solution Service Manual
Connection of branch pipe
The Y-type branch pipe is installed with additional tube. The purpose is to adjust the different pipe
diameters. If the pipe size selected on site is different from the size of branch connector, please
use the pipe cutter to cut from the middle of different connection pipes and remove the burrs. Then,
insert the copper pipe to appropriate depth. The branch pipes from Gree are all provided with
positioning mark.
The connection method that copper pipe is in couple with a smaller branch pipe shall not be used.
Copper pipe
Correct connection
Wrong connection
Copper pipe shall not be inserted too much for connection with branch pipe.
Copper pipe
Cut from the middle of copper
pipe as needed
Copper pipe
Correct connection
Wrong connection
Branch pipe
Branch pipe
Branch pipe
INSTALLATION
182