Representation of analog values
C.3 Analog value representation for resistance-type transmitters / resistance thermometers
C.3
Analog value representation for resistance-type transmitters /
resistance thermometers
C.3.1

Resistance-type transmitters 150, 300, 600, 6000 Ohm

The following tables list the decimal and hexadecimal values (codes) of the possible
resistance-based sensor ranges.
Table C- 6
Resistance-based sensors of 150 Ω, 300 Ω, 600 Ω, and 6000 Ω
Values
dec
hex
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
C.3.2

Thermal resistor Pt 10, 50, 100, 200, 500, 1000 Standard/GOST

Thermal resistor Pt x0 Standard and Pt x0 GOST Standard
Table C- 7
Thermal resistor Pt x0 Standard (0.003851, 0.003916, 0.003902, 0.003920) and Pt x0 GOST Standard
(0.003910)
Pt x0 Stan-
Units
dard in °C
dec
(1 digit =
0.1°C)
> 1000.0
32767
1000.0
10000
:
:
850.1
8501
850.0
8500
:
:
-200.0
-2000
-200.1
-2001
:
:
-243.0
-2430
< -243.0
-32768 8000
74
Resistive transmitter range
150 Ω
300 Ω
>176.38 Ω
>352.77 Ω
176.38 Ω
352.77 Ω
150 Ω
300 Ω
112.5 Ω
225 Ω
5.43 mΩ
10.85 mΩ
0 Ω
0 Ω
Pt x0 Stan-
dard in °F
hex
(1 digit = 0.1
°F)
7FFF
> 1832.0
2710
1832.0
:
:
2135
1562.1
2134
1562.0
:
:
F830
-328.0
F82F
-328.1
:
:
F682
-405.4
< -405.4
600 Ω
>705.53 Ω
705.53 Ω
600 Ω
450 Ω
21.70 mΩ
0 Ω
Units
Pt x00 Stan-
dard in K
dec
hex
(1 digit = 0.1
K)
32767
7FFF
> 1273.2
18320
4790
1273.2
:
:
:
15621
3D05
1123.3
15620
3D04
1123.2
:
:
:
-3280
F330
73.2
-3281
F32F
73.1
:
:
:
-4054
F02A
30.2
-32768
8000
< 30.2
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
6000 Ω
>7055.3 Ω
Overflow
7055.3 Ω
Overshoot range
6000 Ω
Rated range
4500 Ω
217 mΩ
0 Ω
Units
Range
dec
hex
32767
7FFF
Overflow
12732
31BC
Overshoot
range
:
:
11233
2BE1
11232
2BE0
Rated range
:
:
732
2DC
731
2DB
Undershoot
range
:
:
302
12E
32768
8000
Underflow
Manual, 09/2016, A5E36647959-AB