Siemens simatic s7-1500 User Manual page 30

Analog input module ai 8xu/r/rtd/tc hf
Hide thumbs Also See for simatic s7-1500:
Table of Contents

Advertisement

Parameters/address space
4.2 Parameters
Parameters
Hardware interrupts
Hardware interrupt low
limit 1
Hardware interrupt high
limit 1
Hardware interrupt low
limit 2
Hardware interrupt high
limit 2
If you enable diagnostics for multiple channels, you will receive an alarm surge on failure of the supply voltage because
1)
each enabled channel will detect this fault.
You can prevent this message burst by assigning the diagnostics function to one channel only.
You can set the effective range of the diagnostics for each channel in the user program with data records 0 to 8.
2)
The setting is only possible for channels 0 to 7. If you use the "Reference channel of the module" setting for at least one
3)
channel, you need to operate channel 8 with the resistance thermometer RTD measurement type.
You can configure the "Fixed reference temperature" setting and the limits for hardware interrupts in the user program
4)
with data records 0 to 8.
30
Range of values
Default set-
ting
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
Parameter
Scope with configuration software,
assignment
in RUN
Integrated in
the hardware
catalog
STEP 7
(TIA Portal) as
of V12 or GSD
file PROFINET
IO
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
e.g., STEP 7 (TIA Portal)
GSD file
PROFIBUS DP
---
4)
---
4)
---
4)
---
4)
Manual, 09/2016, A5E36647959-AB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp

Table of Contents