Parameters/address space
4.2 Parameters
The following parameter settings for the channels are possible:
Table 4- 2
Configurable parameters and their defaults
Parameters
Diagnostics
Missing supply voltage L+
•
Overflow
•
Underflow
•
Reference channel error
•
Wire break
•
Measuring
Measurement type
•
Measuring range
•
Operating mode
•
Temperature coefficient
•
Temperature unit
•
28
Range of values
Default set-
ting
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
See section Measur-
Thermal
ing types and ranges
resistor RTD
(Page 24)
(4-wire con-
nection
Pt100 stand-
ard
Standard
Standard
•
Fast
•
Pt: 0.003851
0.003851
Pt: 0.003902
Pt: 0.003910 GOST
Pt: 0.003916
Pt: 0.003920
Ni: 0.006170 GOST
Ni: 0.006180
Ni: 0.006720
Cu: 0.00426 GOST
Cu: 0.00427
Cu: 0.00428 GOST
LG-Ni: 0.005000
°C
Kelvin (K)
•
Fahrenheit (°F)
•
Celsius (°C)
•
Parameter
Scope with configuration software,
assignment
in RUN
Integrated in
the hardware
catalog
STEP 7
(TIA Portal) as
of V12 or GSD
file PROFINET
IO
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
e.g., STEP 7 (TIA Portal)
GSD file
PROFIBUS DP
Module
1)
2)
Module
2)
Module
2)
Module
2)
Module
2)
Channel
Channel
---
4)
Channel
Module
Manual, 09/2016, A5E36647959-AB