Siemens simatic s7-1500 User Manual page 17

Analog input module ai 8xu/r/rtd/tc hf
Hide thumbs Also See for simatic s7-1500:
Table of Contents

Advertisement

The following example shows the scaled measuring range with 2 decimal places for a
thermal resistor Pt 100 standard.
At the scaled measuring range with 2 decimal places, the measured value lies between -
325.12 K and +325.11 K around the measuring range center. In the figure, the measuring
range center is drawn at 850 °C.
The measuring range is cut off at 150.00 K, because the limit to the overflow has been
exceeded at 1000 °C (clipping).
Figure 2-4
Scalable measuring range with 2 decimal places that is cut off at the overflow (clipping).
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
Manual, 09/2016, A5E36647959-AB
Product overview
2.2 Functions
17