BASIC GENERATOR SET
Length overall
Width
Height
Weight (Approximate)
TRAILER-MOUNTED GENERATOR SET
Length overall
Width
Height
Weight (Approximate)
Output power rating
Output voltage
Rated load capacity
Frequency (cycles-per-second)
Output kilowatts
Power factor
Duty cycle
Operating speed at 400 Hz
Overload capacity (125% of rated load capacity)
Overvoltage relay
Undervoltage relay
Overfrequency relay
Underfrequency relay
Overload relay
Undervoltage time delay relay
Manufacturer
Model
Type
Displacement
Compression ratio
Firing order
Horsepower at 2000 RPM
Governed speed
Idle speed
Electrical system
Oil capacity (with filter)
Oil capacity (without filter)
Coolant capacity (approx.)
Fuel
Lube oil
December 31/91 Revised
PHYSICAL
GENERATOR
216 A
GENERATOR PROTECTIVE SYSTEM
trips 130 V to 134 V; resets 125 V
trips 102 V or below; resets 110 V
trips 415 Hz to 425 Hz; resets 410 Hz
trips 375 Hz to 385 Hz; resets 385 Hz
trips 112 KVA in less than 5 minutes
4 to 12 seconds
ENGINE
6.3544
In-line, 6-cylinder, 4-cycle Diesel
354 cu. in. (5.8 liters)
16:1
1-5-3-6-2-4
107
2000 RPM +/- 4.5%
850 +/- 25 RPM
12 volt
15 quarts (14 liters)
14quarts (13.6 liters)
20 quarts (19 liters)
Diesel oil conforming to ASTM Specification
D.975-66T, Nos. 1-D and 2-D
MIL-L-2104C or MIL-L-2104D
Specifications and Capabilities
Figure 2
84 inches (2134 mm)
33 inches (838 mm)
43 inches (1092 mm)
3655 pounds (1658 kg)
90 inches (2286 mm)
66 inches (1676 mm)
57 inches (1448 mm)
4120 pounds (1868.5 kg)
60 KVA
115/200 V
173 A
400 Hz
48 KW
0.8 PF
100%
2000 RPM
Perkins Diesel
OM-2053
1-1