Siemens S7-300 Installation And Operating Manual page 264

Hide thumbs Also See for S7-300:
Table of Contents

Advertisement

Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Electrical isolation
Permitted potential difference
Insulation test voltage
Current consumption
Common-mode voltage (CMV)
Power loss of the module
Analog value generation
Measuring principle
Integration/conversion time
Smoothing of measured values (per channel)
264
Between channels 0/1/2 and 3/4/5, backplane
bus, load voltage L+/sensor supply Vs0...5,
shield
Between channels 3/4/5 and 0/1/2, backplane
bus, load voltage L+/sensor supply Vs0...5,
shield
Between backplane bus and channels 0/1/2,
channels 3/4/5, load voltage L+/sensor supply
Vs0...5, shield
Between load voltage L+/sensor supply Vs0...5
and channels 0/1/2, channels 3/4/5, backplane
bus, shield
Between shield and channels 0/1/2, channels
3/4/5, backplane bus, load voltage L+/sensor
supply Vs0...5
Between the channels of a potential group
Between the potential groups
Between the channels (0/1/2 or 3/4/5) of a
potential group
From backplane bus
From supply voltage L+ (without load)
Permitted common mode voltage between the
inputs (U
)
CM
Permitted common mode voltage between the
inputs and M
Assignable
Integration time
At 50 Hz
At 60 Hz
Response time per channel pair
At 50 Hz
At 60 Hz
Basic response time
Resolution, including overrange
Technical data
Yes
Yes
Yes
Yes
Yes
No
75 V DC, 60 V AC
75 V DC, 60 V AC
370 V AC for 1 min.
90 mA, maximum
Typ. 150 mA
75 V DC, 60 V AC
75 V DC, 60 V AC
4.5 W, typical
DELTA-SIGMA
Yes
20 ms
16.67 ms
25 ms
22 ms
50 ms
15 bits + sign
Yes, assignable
Installation and Operating Manual, 01/2010, A5E00085586-10