Shutting Generator Down While Under Load; To Turn The Generator Off; To Turn The Generator Back On - Generac Power Systems 0K2502SPFR Owner's Manual

60 hz air-cooled generator
Table of Contents

Advertisement

Available languages

Available languages

Shutting Generator Down While
Under Load
IMPORTANT NOTE: To turn the generator off during
utility outages to perform maintenance, or conserve fuel,
follow these steps:
To turn the generator OFF (while running in
AUTO and online):
1. Turn the main utility disconnect OFF.
2. Turn the main line circuit breaker (MLCB) on the
generator to OFF (OPEN).
3. Turn the generator OFF.

To turn the generator back ON:

1. Put the generator back into AUTO and allow to
start and warm-up for a few minutes.
2. Set the MLCB on the generator to ON.
The system will now be operating in automatic mode.
The main utility disconnect can be turned ON (CLOSED).
To shut the unit OFF, this complete process must be
repeated.
Owner's Manual for 60 Hz Synergy Generator™
Operation
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents