Thank you for purchasing this model of the standby the operator read this Owner's Manual and thor- generator set product line by Generac Power Systems. oughly understand all instructions before using this Every effort was expended to make sure that the equipment.
Table of Contents Generac Standby Generator Sets Introduction ........Inside Front Cover 2.3 EMERGENCY CIRCUIT ISOLATION METHOD ..8 Read This Manual Thoroughly........IFC 2.4 TOTAL CIRCUIT ISOLATION METHOD ....9 Operation and Maintenance ........IFC 2.5 GROUNDING THE GENERATOR ......9 How to Obtain Service ..........IFC 2.6 GENERATOR AC NEUTRAL CONNECTIONS ..9 Authorized Service Dealer Locator Number....IFC 2.7 TRANSFER SWITCH START SIGNAL...
Important Safety Instructions Generac Standby Generator Sets SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment. SAVE THESE INSTRUCTIONS –...
Page 5
Important Safety Instructions Generac Standby Generator Sets • Inspect the generator regularly, and promptly • Generators installed with an automatic transfer repair or replace all worn, damaged or defective switch will crank and start automatically when parts using only factory-approved parts. normal (utility) source voltage is removed or is below an acceptable preset level.
Section 1 – General Information Generac Standby Generator Sets IDENTIFICATION RECORD ENGINE PROTECTIVE DEVICES The standby generator may be required to operate for 1.1.1 DATA PLATE long periods of time without an operator on hand to monitor such engine conditions as coolant tempera- Every generator set has a metal DATA PLATE that ture, oil pressure or rpm.
Section 1 – General Information Generac Standby Generator Sets 1.3.6 OVERCRANK SHUTDOWN SPECIFICATIONS After a prespecified duration of cranking, this func- 1.6.1 GENERATOR tion ends the cranking if the engine has failed to start. Refer to the data plate on your particular generator for rated watts, amperes, frequency, voltage, phase 1.3.7 RPM SENSOR LOSS SHUTDOWN and other pertinent information.
Section 1 – General Information Generac Standby Generator Sets Engine Electrical System: GENERATOR AC LEAD DC Alternator Output ..........42 amps at 12 volts CONNECTIONS Starter Motor................12-volt DC The electrical wires in the unit’s AC connection Recommended Battery ........One 12-volt, 90 Ah, 27 F (lower) panel should be installed according to the Ground Polarity ..............Negative (–) number of leads and the voltage/phase required for...
Section 2 – Installation Generac Standby Generator Sets STARTING AIDS Figure 1.3 – Typical Dual-rate Battery Charger This standby generator is equipped with the following starting aids that serve to provide quicker, easier starts under varying climactic conditions. This generator has been mounted with an engine coolant heater and a battery charger.
Section 2 – Installation Generac Standby Generator Sets NOTE: • Permits the LOAD circuits to be connected to only one power supply at a time. For more information about the installation of a • Prevents electrical backfeed between the generator standby system, you can order Engine-Generator and the UTILITY power circuits.
Section 2 – Installation Generac Standby Generator Sets TOTAL CIRCUIT ISOLATION GENERATOR AC NEUTRAL METHOD CONNECTIONS When a generator capable of powering all electrical Generac uses an UNGROUNDED AC neutral. loads in the circuit is to be installed, you may use the Grounding is recommended only at the main service “Total Circuit Isolation Method.”...
Section 2 – Installation Generac Standby Generator Sets Storage batteries give off explosive hydrogen • DO NOT SMOKE when near batteries, gas. This gas can form an explosive mixture • DO NOT cause flame or spark in battery area, and around the battery for several hours after •...
Section 2 – Installation Generac Standby Generator Sets 2.9.1.1 Transfer Switch 2.9.1.5 Belt Tension If this generator is used to supply power to any elec- Check the engine fan belt tension and condition prior trical system normally powered by an electric utility, to placing the unit into service and at recommended the National Electrical Code requires that a transfer intervals.
Section 4 – Maintenance Generac Standby Generator Sets GENERATOR CONTROL AND 4.1.2.2 Every Six Months or Every 200 Hours (whichever comes first) OPERATION • Change engine oil and filter. Refer to the appropriate control panel operator’s • Lubricate engine controls. manual for this unit.
Section 4 – Maintenance Generac Standby Generator Sets PERIODIC MAINTENANCE 4.2.2 INSPECT BATTERY A rigorous program of scheduled periodic mainte- DANGER nance should be established and maintained. Such a program, if adhered to diligently, will provide added Standby generators installed with automatic assurance that your power system functions proper- transfer switches will crank and start automati- ly when it is needed.
Section 4 – Maintenance Generac Standby Generator Sets 4.2.3 BATTERY REPLACEMENT REPAIR PARTS The latter portion of this manual consist of exploded When replacing batteries, use the same number and views, parts lists and electrical data pertaining to this the following type batteries. generator set.
Section 5 — Installation Generac Standby Generator Sets Installation Diagram – Drawing No. 0E5195 Generac ® Power Systems, Inc. 15...
Page 18
Section 6 — Electrical Data Generac Standby Generator Sets Wiring Diagram - E Panel – Drawing No. 0D2378V-B WIRE COLOR FUNCTION WIRE #'s LEGEND WHITE NEUTRAL 0,1,R15,591 BLACK/485+ NON-FUSED DC 4,13,29,218 CLEAR/485- ORANGE FUSED DC 14,15,219,220 BARE 56,56A,57-59,67,89 BROWN CONTROL 162,178,183,S1-3,590 2,49,150,A1-8,R1-9 BLUE...
Page 44
Section 7 — Exploded Views and Parts Lists Generac Standby Generator Sets Exhaust (Model 004810-0) – Drawing No. 0E5167 2.5" Dia. Clamp Assembly Engine Compartment Front ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 080762 BOLT U 3/8-16 X 2.62...
Page 45
Section 7 — Exploded Views and Parts Lists Generac Standby Generator Sets Air Duct – Drawing No. 0E1280 ITEM PART NO. QTY. DESCRIPTION 0A6984 BRACKET AIR DUCT TOP/BOTTOM 0A6982 BRACKET AIR DUCT RH SIDE 0A6983 BRACKET AIR DUCT LH SIDE 022413 SCREW HHC 1/4-20 X 1 G5 022097...
Page 46
Section 7 — Exploded Views and Parts Lists Generac Standby Generator Sets Electronic Governor – Drawing No. 0E1818-A TO CONTROLLER (BLACK / WHITE STRIPE & WHITE) CHASSIS INSIDE CONTROL PANEL TO FLYWHEEL HOUSING FACTORY THROTTLE CONTROL ARM TO CONTROLLER (PURPLE WIRES) 76.2±1.6 [3±1/16"] ITEM PART NO.
Warranty (ECS Warranty), which is provided to you by Generac pursuant to federal and California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new non-road diesel engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circum- stances where the Generac Warranty may provide a longer warranty period.
Page 51
Section 9 – Warranty Generac Standby Generator Sets EMISSION CONTROL SYSTEM WARRANTY Emission Control System Warranty (ECS Warranty) for 1996 and later model year non-road diesel engines: (a) Applicability: This warranty shall apply to 1996 and later model year non-road diesel engines. The ECS Warranty shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 60 months, or 3,000 hours of use, thereafter, whichever occurs first.
Page 52
Generac Service Facility, and only applies to permanently wired and mounted units. • A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a Non - Generac Power Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the genset, no warranty coverage shall apply.