Installation and Owner’s Manual Air-cooled Automatic Standby Generators Models: 04673-1 (6 kW NG, 7 kW LP) 04674-1 (12 kW NG, 12 kW LP) 04675-2 (13 kW NG, 15 kW LP) GENERAC POWER SYSTEMS, INC. *This manual should remain with the unit.* Not intended for use as Primary Power in place of utility or in life-support applications.
Guardian models: If any portion of this manual is not understood, contact • 04673-1 – 6 kW NG, 7 kW LP , single-cylinder GH- the nearest Generac Authorized Dealer for starting, 410 Engine operating and servicing procedures.
Table of Contents Generac Air-cooled 7 kW, 12 kW and 15 kW Generators Introduction ......Inside Front Cover 3.2.2 “Off” Position ........14 Read This Manual Thoroughly ......IFC 3.2.3 “Manual” Position ......14 Contents ............IFC Automatic Transfer Operation ....14 Operation and Maintenance ......IFC Sequence of Automatic Operation....14 How to Obtain Service ........IFC Manual Transfer Operation ......15...
IMPORTANT SAFETY INSTRUCTIONS Generac Air-cooled 7 kW, 12 kW and 15 kW Generators SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
IMPORTANT SAFETY INSTRUCTIONS Generac Air-cooled 7 kW, 12 kW and 15 kW Generators • Keep a fire extinguisher near the generator at all ELECTRICAL HAZARDS times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extin- •...
Section 1 — General Information Generac Air-cooled 7 kW, 12 kW and 15 kW Generators PROTECTION SYSTEMS DANGER Unlike an automobile engine, the generator may have Only qualified electricians or contractors should to run for long periods of time with no operator pres- attempt such installations, which must comply ent to monitor engine conditions.
Section 1 — General Information Generac Air-cooled 7 kW, 12 kW and 15 kW Generators FUEL REQUIREMENTS 3. Disconnect wire #0 and wire #14 from the gas solenoid located on the top of the demand regu- AND RECOMMENDATIONS lator. With LP gas, use only the vapor withdrawal 4.
Section 1 — General Information Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 5. Remove the small brass hose fitting from the idle LOCATION circuit port of the regulator housing. ◆ 1.9.1 GENERATOR 6. Remove the small jet (0D5698A) located in the side of the regulator housing and install it into the Install the generator set, in its protective enclosure, small threaded hole in the idle circuit port on the...
Section 1 — General Information Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 1.10 BATTERY INSTALLATION NOTE: Fill the battery with the proper electrolyte fluid if nec- The generator is equipped with a battery trickle essary and have the battery fully charged before charger that is active when the unit is set up for installing it.
Section 2 — Post Installation Start-up and Adjustments Generac Air-cooled 7 kW, 12 kW and 15 kW Generators The following procedures are to be observed: CHECK TRANSFER SWITCH • Wear full eye protection and protective clothing; OPERATION • Where electrolyte contacts the skin, wash it off Refer to Section 3.5 of the owner’s manual for manu- immediately with water;...
Section 2 — Post Installation Start-up and Adjustments Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 8. Connect an accurate AC voltmeter and a frequen- 8. Turn ON electrical loads. Apply an electrical load cy meter across transfer switch terminal lugs E1 equal to the full rated wattage/amperage capacity and E2.
Section 3 — Operation Generac Air-cooled 7 kW, 12 kW and 15 kW Generators ADJUSTING THE REGULATOR Figure 2.2 — Placement of Regulator (NATURAL GAS ONLY) Although the generator has been factory set to pro- vide maximum power, it may be necessary in some areas to adjust this setting.
Section 3 — Operation Generac Air-cooled 7 kW, 12 kW and 15 kW Generators ◆ Figure 2.3 — Engine Governor Adjustment 2.7.3 ADDITIONAL CORROSION PROTECTION Periodically spray all engine linkage parts and brack- ets with corrosion inhibiting spray such as WD-40 or a comparable product.
Section 3 — Operation Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 8. Turn ON the utility power supply to the transfer AUTOMATIC TRANSFER switch, which will allow the transfer switch to OPERATION transfer back to utility power. The unit will con- To select automatic operation, do the following: tinue to run for one minute and then shut down.
Section 3 — Operation Generac Air-cooled 7 kW, 12 kW and 15 kW Generators D.Utility Voltage Pickup Sensor Figure 3.2 – Manual Transfer Switch Operation • This sensor monitors utility power supply volt- age. When that voltage is restored to above 70 percent of the nominal source voltage, a retrans- fer time delay starts timing.
Section 3 — Operation Generac Air-cooled 7 kW, 12 kW and 15 kW Generators SETTING THE EXERCISE TIMER Figure 3.3 – Low Oil Pressure and High Temperature Switches The generator is equipped with an exercise timer. Once it is set, the generator will start and exercise Low Oil Switch High Temp Switch once every seven days, on the day of the week and at...
Section 4 — Maintenance Generac Air-cooled 7 kW, 12 kW and 15 kW Generators FUSE Figure 4.2 — Oil Dipstick and Fill, 7 kW The generator panel’s 15 amp fuse (Figure 4.1) protects Oil Dipstick and Fill the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel.
Section 4 — Maintenance Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 4.3.2 OIL CHANGE PROCEDURE CHANGING THE ENGINE AIR CLEANER To change the oil, proceed as follows: 1. Run the engine until it is thoroughly warmed up 4.5.1 7 KW, 12 KW AND 15 KW then shut OFF the engine.
Section 4 — Maintenance Generac Air-cooled 7 kW, 12 kW and 15 kW Generators SPARK PLUG(S) • Remove watches, rings or other metal objects; • Use tools with insulated handles; Reset the spark plug(s) gap or replace the spark • Wear rubber gloves and boots; plug(s) as necessary.
Section 4 — Maintenance Generac Air-cooled 7 kW, 12 kW and 15 kW Generators ADJUSTING VALVE CLEARANCE • Install new valve cover gasket. • Re-attach the valve cover. After the first 50 hours of operation, adjust the valve NOTE: clearance in the engine. Start all four screws before tightening or it will not Important: If feeling uncomfortable about doing this be possible to get all the screws in place.
Section 4 — Maintenance Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 4.10 ATTENTION AFTER SUBMERSION 4.12.2 RETURN TO SERVICE If the generator has been submerged in water, To return the unit to service after storage, proceed it MUST NOT be started and operated. Following any sub- as follows: mersion in water, have a Generac Authorized Dealer thor- 1.
Section 4 — Maintenance Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 4.13 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by the nearest Generac Authorized Dealer. SYSTEM/COMPONENT PROCEDURE FREQUENCY X = Action Inspect Change Clean W = Weekly...
Section 5 — Troubleshooting Generac Air-cooled 7 kW, 12 kW and 15 kW Generators TROUBLESHOOTING GUIDE PROBLEM CAUSE CORRECTION The engine will not crank. 1. Fuse blown 1. Replace 15A fuse on generator control panel. 2. Loose, corroded or defective 2.
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators Enclosure – Drawing No. 0D3416-R PRE PACKAGED UNITS ONLY 44 85 79 80 49 49 32 Generac ® Power Systems, Inc.
Page 35
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators Enclosure – Drawing No. 0D3416-R ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 0C6140 ASSEMBLY, ENCLOSURE BASE 0D3037A LATCH, QUARTER TURN NON-LOCKING 0D1901 ASSEMBLY, ENCLOSURE BASE (7KW) 0A2115...
Page 36
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators Control Panel – Drawing No. 0E7974-D 34 Generac ® Power Systems, Inc.
Page 37
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators Control Panel – Drawing No. 0E7974-D ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 0E7886A CIRCUIT BREAKER 30A X 2P 240V 0D5240 SWITCH, SPST (ON)-ON N/O (7KW)
Page 38
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990 Engine – Drawing No. 0E8774-F Part 1 36 Generac ® Power Systems, Inc.
Page 39
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990 Engine – Drawing No. 0E8774-F Part 1 ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 0C5729 ASSEMBLY, CRANKCASE HOUSING WITH 0C3971C ASSEMBLY, DIPSTICK WITH HANDLE SLEEVE...
Page 40
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990/760 Engine – Drawing No. 0E8774-F Part 2 123, 145 38 Generac ® Power Systems, Inc.
Page 41
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990/760 Engine – Drawing No. 0E8774-F Part 2 ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 0C5136A KNOB, AIR CLEANER 0C3022A HOUSING, BLOWER NG COOLER 0C3024...
Page 42
Section 7 — Exploded Views and Parts Lists Generac Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW Generator – Drawing No. 0D3504-D 40 Generac ® Power Systems, Inc.
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period.
Section 10 – Warranty Generac Air-cooled 7 kW, 12 kW and 15 kW Generators EMISSION CONTROL SYSTEM WARRANTY Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con- tinue for 24 consecutive months thereafter.
Page 56
FOR GENERAC RESIDENTIAL AND LIGHT COMMERCIAL UNITS For a period of two (2) years or two thousand (2,000) hours of operation from the date of sale, which ever occurs first, Generac Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below.