POWER SYSTEMS, INC. *This Manual Should Remain With The Unit* ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS Owner’s Manual SHOULD ATTEMPT INSTALLATION!! Liquid-cooled, Prepackaged Standby Generators Models: 004373-1 (40 kW/Single-phase w/ 200 Amp Transfer Switch) 004626-0 (40 kW/Single-phase w/ 200 Amp Transfer Switch California Emissions) ®...
INTRODUCTION Thank you for purchasing the Guardian product line by Generac Power Systems. This model is a compact, high performance, liquid-cooled, engine-driven gen- erator designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation.
If you use a procedure, work method or operating technique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and others. You also must make sure the procedure, work method or operating technique that is chosen does not render the generator unsafe.
Keep the area surrounding the generator clean and free from debris. Never disconnect the • Generac generator sets may operate using one of sev- eral types of fuels. FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels.
The generator’s weight of more than 2,000 pounds requires proper tools and equipment, and qualified personnel to be used in all phases of handling and unpacking. Generac Power Systems, Inc. ® THE GENERATOR This liquid-cooled, Guardian generator set is designed to supply electrical power to operate critical electrical loads during utility power failure.
The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. Generac uses an AGC fuse rated at 15 amps. 1.7 SPECIFICATIONS 1.7.1 GENERATOR...
Fuel Consumption Natural Gas 004373-1 & 004626-0 ...720 cfh LP Gas 004373-1 & 004626-0 ...288 cfh/7.9gph Generac Power Systems, Inc. ® FUEL REQUIREMENTS AND RECOMMENDATIONS With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank.
Using any high silicate antifreeze boosters or additives also will cause overheating. Generac also recommends that any soluble oil inhibitor NOT be used for this equipment. 1.11 EMISSIONS CONTROL SYSTEM...
Connecting this generator to an electrical system normally supplied by an electric utility shall be by means of a transfer switch (such as the Generac “GTS” type transfer switch), so as to isolate the electric system from the utility distribution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.
Figure 2.2 – Generator Grounding Lug (typical) 2.5 GENERATOR AC NEUTRAL CONNECTIONS Generac uses an UNGROUNDED AC neutral. Grounding is recommended only at the main service entrance. 2.6 TRANSFER SWITCH START SIGNAL CONNECTIONS 2.6.1 “GTS” Type Switch...
• Wear full eye protection and protective clothing, • Where electrolyte contacts the skin, wash it off immediately with water, 10 Generac Power Systems, Inc. ® • Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical atten- tion, and •...
On acoustic units, cap plugs also are needed to stay within noise specification limits. permitted. Section 2 — Installation Figure 2.3 - Base Frame Cap Plugs Generac Power Systems, Inc. 11 ®...
This indicates the time the engine-generator has operat- ed, in hours and tenths of hours. Use the hourmeter along with the periodic maintenance schedule for your generator set. 12 Generac Power Systems, Inc. ® 3.1.6 AUTO/OFF/MANUAL SWITCH See Section 3.2.
• The timer will run for about one minute, and the generator will then shut down. 3.5 ENGINE HEATER This Generac standby generator comes equipped with a block heater (Figure 3.2, page 14) that is similar to the block heaters used in automotive applications.
• Place a sign on the generator’s control panel and on 14 Generac Power Systems, Inc. ® the transfer switch that indicates the day and time the generator will be exercising.
4.3 CHANGING THE ENGINE AIR CLEANER To replace the engine air cleaner, (Generac part num- ber 0A4637, simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover.
Air Cleaner Battery replacement Generac uses a Group 27F vented type battery that has 600 CCA @ 0º F . Generac’s part number is 058665. The BCI number should be located directly on the battery. Standby generators installed with automatic...
Once each year, have the generator cleaned and inspect- ed by a Generac/Guardian Authorized Dealer. Service technicians will use dry, low pressure air to clean inter- nal windings. Parts inside the control console should be cleaned and inspected at this time as well.
The same applies for any access ports in the roof of the enclosure. If any of these caps are missing, contact a Generac/Guardian Authorized Dealer. 2. Inside the generator set, the chance of rodent entry into the control panel is greatly reduced by the inclu- sion of adjustable wire connectors.
4.12 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by your nearest Generac/Guardian Authorized Dealer. SYSTEM/COMPONENT X = Action R = Replace/Adjust as Needed * = Notify Dealer if Repair is Needed. FUEL Fuel lines and connections*...
There is no AC output from the generator. There is no transfer to standby after utility source failure. *Contact your nearest Generac/Guardian Authorized Dealer for assistance. 20 Generac Power Systems, Inc. ® CAUSE 1. Fuse blown 2. Loose, corroded or defective battery cables 3.
Section 7 — Exploded Views and Parts Lists (Model No. 004373-1) Guardian Liquid-cooled 40 kW Generators Control Panel - Drawing No. 0D4995-C 30 Generac Power Systems, Inc. ®...
Page 33
WASHER FLAT #8 ZINC NUT HEX #8-32 STEEL NUT HEX #6-32 STEEL SCREW PPHM #6-32 X 1-1/4 SCREW PHTT #6-32 X 1/2 ZYC SCREW PHTT #6-32 X 5/8 ZYC FUSE & HOLDER LITTEL 7.5A REF. FUSE 7.5AXBK/AGC7.5NX Generac Power Systems, Inc. 31 ®...
Page 34
Section 7 — Exploded Views and Parts Lists (Model No. 004626-0) Guardian Liquid-cooled 40 kW Generators Control Panel - Drawing No. 0D6978-A 32 Generac Power Systems, Inc. ®...
Page 35
0C2323 SCREW PHTT #6-32 X 5/8 ZYC 0A2284 SCREW SWAGE 8-32 X 1/2 Z/YC 0C1127 DECAL AVR COVER 0D5324 FUSE & HOLDER LITTEL 7.5A 0A9611 FUSE 7.5AXBK/AGC7.5NX * PART OF CONTROL PANEL WIRE HARNESS Generac Power Systems, Inc. 33 ®...
Page 36
SCREW PPHM M5-0.8 X 16 098647 ASSEMBLY L.C. ELECTRONIC GOVERNOR 036409 NUT HEX 1/4-28 STEEL 0C2184 STUD THR 1/4-28 X 3-1/2 G2 ZINC 34 Generac Power Systems, Inc. ® ITEM (18) NEOPRENE COATING WIRE HARNESS SECURE WIRE HARNESS WITH TIE WRAP AS SHOWN.
Page 37
OPEN SETS. 2) ITEM 25 (PLUG BUTTON 3" DIA.) IS USED AFTER SHIPPING. HOLES ARE TO REMAIN UNCOVERED FOR SHIPPING PURPOSES. PLUGS CAN BE FOUND IN THE MANUAL BAG LOCATED INSIDE THE LOWER CONNECTION BOX. Generac Power Systems, Inc. 35 ®...
Page 38
Section 7 — Exploded Views and Parts Lists (Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generator Engine Common Parts – Drawing No. 0A4304-J 36 Generac Power Systems, Inc. ®...
Page 39
SCREW HHC M10-1.5 X 25 G8.8 0C3756 BOLT TENSIONER PULLEY 045772 NUT HEX M10-1.5 G8 YEL CHR 0D2514 SPARK PLUG 5.7L GM 052259 WASHER FLAT M12 055934D CLAMP VINYL 1.06 X .406 Z 0A37970001 1 FILTER OIL Generac Power Systems, Inc. 37 ®...
Page 40
Section 7 — Exploded Views and Parts Lists (Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators Engine Parts – Drawing No. 0D6980 38 Generac Power Systems, Inc. ®...
Page 42
NOTE: TORQUE ITEM #6 TO 24 FT/LB AND USE THREAD LOCKING COMPOUND (T-13717). To Engine Flywheel To Engine Flywheel Housing Note: Thread in Sensor (8) until contact is made with Ring Gear, then back off 1/2 to 3/4 turn and tighten nut. Caution: Do not rotate engine during this adjustment.
Page 44
PADDLE HANDLE LOCK 0C6748 NUT LOCK HEX M4-0.7 SS NYL INS 080490 WASHER FLAT #8 SS 087233 RIVET POP 3/16 X 1/4 0C4065 (A) DUCT FRONT LH 42 Generac Power Systems, Inc. ® BASE FRAME ITEM PART NO. 0C4064 (A) 0C4066 (A)
Page 45
SCREW HHTT M6-1.0 X 12 YC 048031C CLAMP HOSE BAND 1/4 0C4341 SUPPORT RADIATOR A GROUP 046627 CAP RADIATOR Section 7 — Exploded Views and Parts Lists Radiator – Drawing No. 0D4991-A "A" To "A" Generac Power Systems, Inc. 43 ®...
Page 46
HOSE 1IN ID LP GAS (LPG LIQUID) (1’) 0A6344 BARBED ELBOW 90 1/8 NPT X 3/8 047290 HOSE 3/8 ID SINGLE BRAID (.75’) 0A4121 VALVE PCV 44 Generac Power Systems, Inc. ® USE FASTENER LOCATED ON ALTERNATOR FAN SCROLL REGULATOR TO STEPPER...
Page 47
CONNECTOR C/C VENT 0A5737C SPACER DC ALTERNATOR 0C7060 GASKET CARBURETOR ADAPTOR 022152 WASHER LOCK #10 064090 SCREW PHM SEMS #12-24 X 5/8 EX 0C7908 SCREW SHC #10-32 X 5/8 G8.8 NZ * NOT SHOWN Generac Power Systems, Inc. 45 ®...
Page 48
030795 SCREW HHC 5/16-18 X 1 G5 025655 PLUG STD PIPE 3/4 STEEL SQ HD 022132 WASHER FLAT 9/16 ZINC 051778 SCREW HHC M14-2.0 X 25 G8.8 46 Generac Power Systems, Inc. ® CARBURETOR ITEM PART NO. 028641 057824 057422...
Page 49
WASHER LOCK SPECIAL 5/16 022259 NUT HEX 5/16-18 STEEL 058359 LUG RNGTNG INS 22-18 X 5/16 X .477 0D2616 SUPPORT REGULATOR 0D1509 DECAL,INLET PRESSURE * NOT SHOWN NOTE: ITEM #22 ATTACHES TO ALTERNATOR SCROLL Generac Power Systems, Inc. 47 ®...
Page 50
NUT, HEX-M6 X 1.00 G8 YEL CHR 042568 SCREW, HHC-M6-1.0 x 20MM G8.8 **077043E 36" FLEXIBLE CONDUIT 1" BLACK *USED ON "R" VOLTAGE GENERATORS ONLY **ITEM #14 USED ONLY ON 4.3L UNITS 48 Generac Power Systems, Inc. ® Lower Radiator To Water Hose Pump To Engine...
Page 51
SCREW HHC 3/8-16 X 3/4 G5 022131 WASHER FLAT M10-3/8 ZINC 025507 WASHER SHAKEPROOF EXT 7/16 STL 022237 WASHER LOCK 3/8 Section 7 — Exploded Views and Parts Lists Battery – Drawing No. A6708-F TO STARTER SOLENOID BLACK Generac Power Systems, Inc. 49 ®...
Page 52
Section 7 — Exploded Views and Parts Lists (Model Nos. 004373-1 & 004626-0) Guardian Liquid-cooled 40 kW Generators Lower Panel – Drawing No. 0D5334-B 50 Generac Power Systems, Inc. ®...
EXHAUST OUTLET - LIFTING EYE (4 PLACES) CENTER OF GRAVITY 981 [38.62"] FOR CIRCUIT BREAKER STUB-UP LOCATION. 2.5" OD MUFFLER OUTLET (1) 12V BATTERY SEE NOTE 4 158 [6.22"] 1930 [75.98"] RIGHT SIDE VIEW Generac Power Systems, Inc. 57 ®...
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS" For a period of two years or 2000 hours of operation from the date of original sale, whichever occurs first, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accor- dance with the warranty schedule set forth below.