14.5 ACCESSORIES NOT INCLUDED IN THE SUPPLY

14.5.1 EXTERNAL SENSOR
The External Probe, supplied as an accessory, can be
temperature and vice-versa (the factory setting is 50%-50%).
E.g.
C then
A and C (approx. 6 seconds)
B
"
B
"Temps / mode CH1"
B
B and choose the %
B
C to return to the previous menu.
SETTING THE CLIMATE CURVE Kt
To set the climate curve
.
B
720 (Heating curve slope)
B
(from 0.10 to 4)
Select the climate curve from among those available, see the curve chart in annex "SECTION" E at the end of this manual (the
preset curve is 1.5).
KEY TO CURVE CHART Kt - "SECTION" E
14.5.2 CONNECTING AN EXTERNAL STORAGE BOILER
(for models 1.12 - 1.18 - 1.24 - 1.32)
The heating-only boilers, models 1.12 - 1.18 - 1.24 and 1.32 can be connected to an external storage boiler as they are factory-
supplied as an accessory, to terminals 9-10 of the M2 terminal block. The sensitive element of the NTC probe must be inserted in
the holder provided on the storage boiler. To adjust the temperature of the DHW see section 3.
KEY TO STORAGE BOILER CONNECTIONS (see diagram C in annex "SECTION" G at the end of this manual).
A
Heating Unit
B
C
D
The anti-legionellosis function is NOT ENABLED. To enable it, set parameter 1640 as described below.
To activate the ANTILEGIONELLOSIS
Access MENU 2 as described in section 14.2.1.
B
B
Periodically or
Choose Periodically
procedure described above: set parameter 1641
1644 to set the starting time of the function.
Choose
function.
7219836.01 (1-04/15)
"
B
B
750
access menu 2
B
B
Outside temperature
B
B
B
E
F
Storage boiler unit
G
DHW priority probe
1640 then
48
B
B
1642 to establish
1644 to set the start time of the