8. Commissioning form

Function
Fan speeds
Away, supply air fan
Away, extract air fan
Home, supply air fan
Home, extract air fan
Boost, supply air fan
Boost, extract air fan
Maximum automatic boost, supply air fan
Maximum automatic boost, extract air fan
Smart settings
Cooling, supply air fan
RH, boost limit
RH, full boost
A
+
, Home limit
A
, Away limit
+
AQ, boost limit
AQ maximum boost
Fireplace function, difference in fan speed
Cooker hood function, compensation (home)
Cooker hood function, compensation (boost change)
Central vacuum cleaner function, compensation
Airflows | NOTE! All the fan modes should be preset.
Supply air, total
Away
Home
Boosting
Extract air, total
Away
Home
Boosting
Ventilation unit data |
service company.
Preset by:
!
Important
The supply airflow must be 2–10 % lower than the extract airflow.
Remember to explain the use of the item of optional equipment and how to service it to the user/caretaker!
30
www.swegonhomesolutions.com
Write down the data on the ventilation unit identification plate for reference when the need arises to contact a
Factory setting
40 %
40 %
55 %
55 %
70 %
70 %
100 %
100 %
75 %
5 %
30 %
900 ppm
600 ppm
800 ppm
1,400 ppm
20 %
20 %
0 %
20 %
Project planning values
l/s m
/h
3
l/s m
/h
3
Date:
Swegon reserves the right to alter specifications.
W4.311016