W4 Econo - Swegon CASA W4 Smart Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

7.7.2 W4 Econo

1
5
2
3
4
1: Group electrical distribution box | 2: Electrical equipment cubicle | 3: Exhaust air | 4: Outdoor air | 5: Power supply: 230 V, 10 A
with plug-in connection | 6: The damming height of the water trap, 100 mm | 7: Supply demarcation of the ventilation unit | 8:
Separate extract air, bypasses the heat exchanger | 9: General ventilation | 10: Supply air | 11: Modular cables with RJ9-connectors |
12: Control panel | 13: Cooker hood
SYMBOL
DESIGNATION
TC1
MANUAL TEMPERATURE CONTROL
TV1
AUTOMATIC THERMOSTATIC VALVE
TE3
TEMPERATURE SENSOR
T1
TEMPERATURE SENSOR
T2
TEMPERATURE SENSOR
T3
TEMPERATURE SENSOR
T5
TEMPERATURE SENSOR
T6
TEMPERATURE SENSOR
T7
TEMPERATURE SENSOR
T8
TEMPERATURE SENSOR
TZ02
OVERHEATING PROTECTION
F1 + F2
FILTER
F3
FILTER
HR
HEAT EXCHANGER
SF1
FAN
EF1
FAN
RH
SENSOR
RH + CO2
SENSOR
RH + VOC
SENSOR
DESCRIPTION OF THE FUNCTIONS
CONTROL FUNCTIONS:
The ventilation unit can be operated from a separate Smart control panel or a compatible CASA cooker hood.
When the ventilation unit is controlled from the cooker hood in the Home/Away/Boost modes and for local extraction, the time can be set to 30, 60 or 120 minutes.The
supply air temperature can be manually set with the water-heated air heater thermostat valve. Whenever necessary, the reheating function can be switched off by setting the thermo-
stat to the zero setting.
Summer operation: In the summer, the extract air is steered past the heat exchanger when the controller opens the bypass cover.
Freeze protection for water-heated air heater for reheating: The fans will stop if the return water temperature drops below 10 °C. The fans start again when the return
water temperature reaches the set value 16 °C
The air heater is equipped with a TZ02 automatic thermostat with manual reset (preset limit value 90 °C) as protection against overheating.
The fans have automatic overtemperature protective devices.
IF THE SAFETY EQUIPMENT TRIPS:
If an overheating protection with manual reset trips, it can be reset by pressing a reset button above the air heater.
The automatic overheating protections of the fans will reset themselves when the temperature has dropped below the setting value.
Swegon reserves the right to alter specifications.
6
EXPLANATION
Manual temperature control for the reheating air heater, factory settings 17 °C
Thermostat valve reheating air heater
Thermostat valve's temperature sensor
Temperature sensor, outdoor air
Temperature sensor, supply air downstream of the heat exchanger
Temperature sensor, extract air
Temperature sensor, exhaust air
Freeze protection for water-heated air heater for reheating
Excess temperature sensor for the preheating air heater
Room temperature sensor, accessory, separate cable routing
Overheating protection with manual reset
Supply air filter
Extract air filter
Heat exchanger
Supply air fan
Extract air fan
Moisture sensor
Humidity/carbon dioxide sensor (accessory)
Humidity/VOC sensor (accessory)
11
8
7
www.swegonhomesolutions.com
W4.311016
12
10
13
9
27