Refer to Figures 7 and 10 for information concerning
side and bottom supply and return air duct openings.
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing
compound on male pipe threads. Install a condensate
drain line from the 3/4" NPT female connection on the
unit to an open drain.
The condensate drain operates in a negative
NOTE:
pressure in the cabinet. The condensate drain
line MUST be trapped to provide proper drain-
age. See Figure 1.
Unit Condensate
Connection
3" Min.
2"
Drain
Plug
FIGURE 1 - RECOMMENDED DRAIN PIPING
COMPRESSORS
Units are shipped with compressor mountings factory-
adjusted and ready for operation.
Units with scroll compressors have a shipping bracket
which must be removed after the unit is set in place.
See Figure 2.
Do not loosen compressor mounting bolts.
FILTERS
One-inch or two-inch filters can be supplied with each
unit. Filters must always be installed ahead of the
evaporator coil and must be kept clean or replaced with
8
Base
Pan
Base
Rails
Compressor
Mounting bracket
base
Remove these
screws (2)
Mounting bracket
top (remove)
Wire tie
(cut and remove)
FIGURE 2 - COMPRESSOR RESTRAINING
BRACKET
same size and type. Dirty filters will reduce the capacity
of the unit and will result in frosted coils or safety shut-
down. Minimum filter area and required sizes are
shown in Physical Data Table 4.
SERVICE ACCESS
The following removable panels provide access to all
serviceable components:
•
Compressor compartment
•
Electric Heat compartment
•
Blower compartment
•
Main control box
•
Filter compartment
Refer to the Dimensions and Clearances shown in Fig-
ures 7 and 11 for location of these access panels.
Make sure that all screws and panel latches
are replaced and properly positioned on the
unit to maintain an airtight seal.