Download Print this page

Commissioning - IDEAL Evomax 30 Manual

Multiline flue kit
Hide thumbs Also See for Evomax 30:

Advertisement

4.0 COMMISSIONING

To accommodate the flue pressure generated by the
connection of multiple boilers to a common flue, the minimum
rate (equivalent to minimum fan speed) of each Evomax
appliance operating on the Multiline cascade system is
increased to offset the maximum back-pressure created.
Table 4.1 shows the revised performance of each Evomax
model where it differs from standard standalone operation as
shown in the Evomax Installation & Servicing instructions.
To convert Evomax operation with the Multiline flue as
described, the change is made by accessing the operating
parameters on the Evomax user interface control panel
following the procedure below. This change must be made to
each Evomax operating on the Multiline cascade system.
4.1 EVOMAX CASCADE FLUE SYSTEM – MINIMUM RATE BOILER SETTINGS & DATA
Evomax Boiler Model
Fan Speed
net
Input
gross
Output
non-condensing
Output
condensing
Flue CO
± 0.5
2
NOx
Cat 5
(weighted)
EVOMAX - MULTILINE FLUE KITS
COMMISSIONING
30
30P
rpm
1980
2100
kW
7.6
7.6
kW
8.4
8.3
kW
7.5
7.5
kW
8.0
7.8
%
9.0
10.6
mg/kWh
33
82
Procedure for selecting Multiline cascade flue operation
on Evomax user interface control panel.
1.0
Press SELECT and then hold + and – buttons down
together for more then 5 seconds, the following screen
will be displayed.
INSTALLER MODE
NORMAL OPERATION
SET FLOW TEMP'
SET DHW TEMP'
2.0
Rotate the KNOB clockwise and scroll downwards
towards the end of the list until the following screen is
displayed.
INSTALLER MODE
FLAME/LPG RELAY
FLUE SETTING
NORMAL OPERATION
3.0
Press SELECT and the following screen will be
displayed.
INSTALLER MODE
STANDARD FLUE
MULTILINE FLUE
4.0
Press + or - to highlight 'Multiline Flue' and then press
ENTER to store.
5.0
Rotate the KNOB clockwise until Normal Operation
is highlighted again and press SELECT to return to
normal operation.
40
40P
60
60P
2400
2340
1800
1800
10.1
10.1
15.2
15.2
11.2
11.0
16.9
16.5
10
10
15.0
15.0
10.7
10.4
16.0
15.7
9.0
10.6
9.0
10.6
41
84
35
84
80
80P
100
120
2340
2220
2280
1860
20.5
20.5
25.6
30.7
22.7
22.3
28.4
34.1
20
20
25.0
30.0
21.6
21.2
27.0
32.4
9.0
10.6
9.0
9.0
42
68
43.5
41
150
1800
38.4
42.6
37.5
40.5
9.0
40.5
9

Advertisement

loading