Multiline flue kit
Hide thumbs Also See for Evomax 30:

Advertisement

FIGURE 3.2
(FLUE SYSTEM LAYOUT)
3.3 EVOMAX CASCADE FLUE SYSTEM DATA
Evomax
Cascade System Limits
Model Output
Maximum
Model
System
Capacity
Max
Min
Hmax
kW
kW
kW
30
7.5
40
10
400
60
15
80
20
100
25
120
30
600
150
37.5
30P
7.5
40P
10
400
60P
15
80P
20
EVOMAX - MULTILINE FLUE KITS
'A'
Combustion Products
Data
Maximum
Permissible
max
min
Header
Temperature
rate
rate
Pressure
CO
CO
2
2
'A'
(Static)
Pmax
± 0.5
± 0.5
Pa
%
%
40
9.7
9.0
80
40
11.4
10.6
FLUE DESIGN
Customer specified components
3.4 DESIGN PROCEDURE
1. Determine the required total heat output. (Htot) [maximum
of 6 boilers per system].
2. Determine the required minimum heat output.
3. From Table 3.3 select the Evomax models required.
Max
4. Using Figure 3.5 read the Combustion Products Flow Rate
(Qmax) at the Total System Capacity (Htot).
5. Record the information in Table 3.6
C
6. Calculate the maximum permissible flue length at
conditions Qmax & Pmax.
L = [a – (c + d)] / b (Table 3.6)
72
'A'
At the maximum system
capacity the static pressure
generated against the flue
resistance at position [A]
must not exceed the value
Pmax quoted in Table 3.3.