Mounting

Switching point
10
4 Mounting

4.1 General instructions

In general, SITRANS LVL100 can be installed in any position.
The instrument simply has be mounted in such a way that the
tuning fork is at the height of the desired switching point.
The tuning fork has lateral marking (notches), marking the
switching point with vertical mounting. The switching point
refers to water (1 g/cm³/0.036 lbs/in³). When mounting
SITRANS LVL100, make sure that this marking is at the height
of the requested switching point. Keep in mind that the
switching point of the instrument is shifted if the medium has a
density other than water.
2
1
3
Fig. 2: Vertical mounting
1
Switching point approx. 13 mm (0.51 in)
2
Switching point with lower density
3
Switching point with higher density
SITRANS LVL100 l CONTACTLESS ELECTRONIC SWITCH