Table 2-7
Direction Settings
Sub-menu: System Config.
Setting name
FWD Name Tag
REV Name Tag
2.2.7

Real Time Clock

The date and time can be programmed and then maintained by the internal real time clock. The clock is also
maintained for 2-3 week while the relay is de-energised. Additionally, in order to maintain synchronism within a
substation, all Argus relays can be synchronised to the nearest second or minute using a mapped status input or
via the IEC 60870-5-103 protocol Time Synchronising Frame.
The System Config.:Clock Sync. From Status setting specifies whether the clock will be synchronised to the nearest
minute or second when the status input is activated.
Table 2-8
Real Time Clock Settings
Sub-menu: System Config.
Setting name
Calendar – Set Date
Clock - Set Time
Clock Sync. From Status
Sub-menu: Status Config.
Setting name
Gn Clock Sync
2.2.8

Default Instruments

When a user stops accessing the keypad e.g. on leaving the Sub/Station the relay will, after a user set delay,
automatically switch to default metering whereby the user selected default instruments are displayed in turn at 5
seconds intervals without user intervention. The time before this occurs is programmable with the System
Config.:Default Screen Time setting.
The user can select/deselect the instruments to be displayed in the default metering cycle by going to the
Instrument MODE.: scrolling down to the required default instrument and using the ENTER key. This is described in
detail in the User Manual document, section 1.3.4.
This function enables the user to set the relay to automatically return to displaying ammeters and other
instruments such as ARC Status or Counters. Therefore, essential data is presented to visiting engineers without
the need to negotiate the relay's HMI menu structure
Table 2-9
Default Instrument Setting
Sub-menu: System Config.
Setting name
Default Screen Time
2.2.9

Password

All settings on Argus relays can be password protected. The default password is 'NONE' making the password
protection 'not active' therefore all settings can be edited without the relay requesting a password. If a password is
set by the user then, before a setting can be changed, the set password must be entered. This allows access for
further settings changes to be made without the need to re-enter the password each time. If the user then leaves
©2013 Siemens Protection Devices Limited
Range (bold = default)
ABCDEFGHIJKLMNOPQRSTUV
WXYZ1234567890 -+/
(FWD)
ABCDEFGHIJKLMNOPQRSTUV
WXYZ1234567890 -+/
(REV)
Range (bold = default)
DD/MM/YY (01/01/00)
HH:MM:SS (00:00:00)
Minutes, Seconds
Range (bold = default)
_, 1 for each status input
(default: _ _ _ _ _ _ _ _ _)
Range (bold = default)
10 sec, 60 sec, 5 min, 1 hour
7SG11 Argus Technical Reference
Units Notes
Argus 2 and Argus 6 only
Up to 13 characters per name
Units Notes
When user presses 'ENTER' after
editing, seconds are zeroed and
clock begins counting.
Units Notes
Default - not mapped to any
status
Units Notes
P20007 Page 25 of 71