The linesman mode is easily reached from the top of the menu tree using the down ( ) key.
If the linesman mode is not required it can be hidden using System Config.:Linesman Display, which is password
protected. This setting allows a controlling setting such as SEF OFF to be set and then hidden such that it cannot
accidentally, or easily, be turned back on again
Table 2-30
Linesman Mode Setting
Sub-menu: System Config.
Setting name
Linesman Display
Table 2-31
Linesman Mode Settings and Commands
Setting name
Scada Control
Hot Line Working
Trip & Lockout
Trip & Reclose
Close & Reclaim
ARC
Inst. Lowset
Trip Counter Reset
SEF
©2013 Siemens Protection Devices Limited
Range (bold = default)
VISIBLE, HIDDEN
Range (bold = default)
OFF, ON
OFF, ON
NO, YES
OFF, ON
OFF, ON
NO, YES
OFF, ON
7SG11 Argus Technical Reference
Units Notes
If attempts are made to access
Linesman mode when it is set to
Hidden the Display will show
'Linesman Display '
hidden'
YES / NO confirmation
Units Note:-
required.
Set to ON for live line working.
When set 'On', detection of a fault
causes an instantaneous trip and
lockout.
Normally set to 'NO', set to 'YES'
and confirm Y to carry out
command.