Waveform (Disturbance) Records - Siemens 7SG11 Manual

Hide thumbs Also See for 7SG11:
Table of Contents

Advertisement

Type
Fault Record Entry
Gn
Group
PHASE A, PHASE B,
Poles
PHASE C, EARTH
FAULT, SEF, REF
FWD (or user tag)
Direction
REV (or user tag)
LS
Elements
DTL
IDMTL
HS1
HS2
TIMER 1
TIMER 2
EXTERNAL TRIP
CB FAIL 1
CB FAIL 1 + 2
<xx>
IA=xxx
Current
IB=xxx
IC=xxx
IE=xxx
ISE=xxx
VA=xxx
Voltage
VB=xxx
VC=xxx
VN=xxx
TRIP & RECLOSE
Auto-reclose
HOT LINE LOCKOUT
TRIP & LOCKOUT
LINE CHECK TRIP
SA TRIP
(user defined text tag)
General Alarms
Example
'12/05/04 17:25:51.2525 G1 PHASE A LS IDMTL <HS1> HS2 IA = 12.32xIn, PHASE B LS IDMTL HS1 HS2 IB = 12.23xIn, PHASE C LS
IC=0.78xIn, EARTH FAULT LS IDMTL IE=0.27xIn', BUCHHOLZ TRIP
This specifies the date and time of the trip and that settings group 1 was active at the time of trip. On phase A the
lowset, delayed characteristic, and highsets 1 and 2 were picked up. Phase A highset 1 issued the trip/fault
trigger. Phase A current was 12.32 xIn. On phase B the lowset, delayed characteristic, highset 1 and highset 2
were picked up with a current of 12.23 xIn. On phase C the lowset element was picked up with a current of 0.78
xIn. The earth-fault lowset and delayed characteristic elements were picked up with a current of 0.27 xIn, and a
General alarm 'BUCHHOLZ TRIP' was raised. Basically a Phase A to B fault with some Earth fault component,
Phase C unfaulted.

2.13.3 Waveform (Disturbance) Records

Waveform Record storage is a digital graphical record of analogue current (and for Argus 2 type II voltage) inputs,
status inputs and relay outputs.
Each record is one second in length and is triggered from a protection element operating or from a status input as
designated in the Data Storage:Waveform Trig setting. This allows the user to specify one or more trigger methods:
©2013 Siemens Protection Devices Limited
Active setting group at time of trip, where n is the group number
Forward and reverse direction. User-defined text tags can be
programmed for each direction, e.g. LINE, BUS, FEEDER,
TRANSFORMER, etc.
Lowset
Time-delayed characteristic (set to DTL)
Time-delayed characteristic (set to IDMTL)
Highset 1
Highset 2
st
SEF/REF 1
time delay
nd
SEF/REF 2
time delay
Trip generated externally and monitored through status input
Circuit breaker fail re-trip
Circuit breaker fail back-trip
Element shown e.g. '< IDMTL >' raised the fault trigger
Current of phase A is xxx
Current of phase B is xxx
Current of phase C is xxx
Current of earth-fault pole is xxx
Current of sensitive or restricted earth-fault pole is xxx
Voltage of phase A is xxx
Voltage of phase B is xxx
Voltage of phase C is xxx
Neutral displacement voltage is xxx
Autoreclose following trip
Recloser locked out following trip, due to hot line working active
Recloser locked out following trip
Trip due to switch onto fault
External trip
A user-defined text tag can be programmed, e.g.' BUCHHOLZ
TRIP '. Multiple Alarms are concatenated with ' + ' symbols
7SG11 Argus Technical Reference
Description
P20007 Page 48 of 71